2-9
Starting Up the Drive for Vector Regulation
Step 5.4 Press the ENTER key to display the default setting of P.001.
This displays the default setting for
acceleration time (20.0 seconds).
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 5.5 Press the
£
key to increase acceleration time, or the
¥
key to decrease
acceleration time.
The adjustment range is:
0.1 to 999.9 seconds.
VALUE ENTERED:
Step 5.6 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
number is displayed. You can now go to the
next parameter.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 5.7 Press the
¥
key to display P.002, Decel Time 1 (RAMP1).
This parameter sets the deceleration time in
seconds. The default stop method is
coast-to-stop, set in P.025.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM