1-6
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 3.7 Press the ENTER key to display the default setting of P.002.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
This displays the default setting for
deceleration time (20.0 seconds).
Step 3.8 Press the
£
key to increase deceleration time, or the
¥
key to decrease
deceleration time.
The adjustment range is:
1.0 to 999.9 seconds.
VALUE ENTERED:
Step 3.9 Press the ENTER key to save the changed value.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
After pressing ENTER, the same parameter
number is displayed. You can now go to the
next parameter.
Step 3.10 Press the
“
key to display P.003, Minimum Speed.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
This parameter sets the minimum speed in
Hz.