4-7
Programming Reference
Control Source (P.000)
Local keypad/display
(P.000 = LOCL)
Terminal strip remote inputs
(P.000 = rE)
Option port (P.000 = OP)
Serial port (P.000 = SErL)
AUTO/MAN Status
AUTO selected
MAN selected
AUTO selected
MAN selected
AUTO selected
MAN selected
AUTO selected
MAN selected
Speed Reference Source
Terminal strip
Local keypad/display or OIM
Terminal strip
Local keypad/display or OIM
Network
Local keypad/display or OIM
Terminal strip
Local keypad/display or OIM
P.000 Control Source
(continued)
Table 4.1 – Speed Reference Source Based on P.000 and AUTO/MAN Key Status
Refer to chapter 3 and the description of parameter P.052 (AUTO/MAN Key
Disable) in chapter 4 for more information on the AUTO/MAN key.
Set P.000 = OP to select the DeviceNet
TM
Network option board, the AutoMax
TM
Network option board, the PROFIBUS™ or the ControlNet
TM
Network option board
as the drive control source.
Note that the REMOTE LED will turn on if any control source other than the local
keypad is selected.
P.001 Accel Time 1 (RAMP 1)
For V/Hz regulation,
this parameter
specifies the amount
of time in which the
motor ramps from
zero speed to
Maximum Speed
(P.004).
For vector regulation,
this parameter
specifies the amount
of time in which the
motor ramps from
zero speed to Motor
Top Speed (U.017).
Parameter Range:
1.0 to 999.9 seconds (V/Hz)
0.1 to 999.9 seconds (vector)
Default Setting:
20.0
Parameter Type:
Tunable
Refer also to parameters: P.004 Maximum Speed
P.005 Current Limit
U.017 Motor Top Speed
The time the motor takes to make any speed increase is directly proportional to the
value in this parameter. This parameter does not apply if JOG is selected. See
P.021 (Jog Ramp Accel Time).