Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
59
AOP Controller Tags
Chapter 6
08 (08)
OSSD2
Check for short circuits at terminal 24 to 24V and 0V.
Processor A shows FF. Processor B shows 08 (24V short).
Processor A shows 82. Processor B shows 08 (0V short).
09 (09)
Low Side
Check for short circuits at terminal 51 and L61 to 24V and 0V.
Processor A shows 09. Processor B shows 0A.
10 (0A)
High Side
11 (0B)
SPI
Follow the general instructions for faults. See
General Instructions for Faults on page 39
12 (0C)
L11
Check for short circuits at terminal L11 to 24V and 0V.
Processor A shows FF. Processor B shows 0C.
13 (0D)
Locking configuration different from
EEPROM
The connections at terminals 51 and L61 differ from the configuration that is stored in the EEPROM. Return to the
previous connections or reconfigure the GLP.
Processor A shows FF. Processor B shows 0C.
14 (0E)
Switch setting different from EEPROM
Logic, Range, or Time switch setting was incorrect on power-up.
Processor A shows FF. Processor B shows 0E (24V short).
Set switch back to appropriate setting or reconfigure the GLP.
15 (0F)
EEPROM
Follow the general instructions for faults. See
General Instructions for Faults on page 39
17 (21)
Compare State
19 (13)
L52
20 (14)
Switch 3
21 (15)
CASE 000
22 (16)
Cross Tran
23 (17)
B2 Value Different from EPROM
In Logic Setting 5…8: Upon power-up, the connection to B2 is not as originally configured. Either reconnect 24V
or remove 24V from B2 and cycle power to the GLP.
24 (18)
IN1 is open while guard switch is locked
Follow the general instructions for faults. See
General Instructions for Faults on page 39
25 (19)
Switch overflow
29 (1D)
B2
30 (1E)
S12
31 (1F)
S22
32 (20)
Main Output Transistor
33 (21)
Overvoltage detected
Measure and adjust the voltage at terminal A1 to 20.4…26.4V under all electrical load conditions.
Processor A shows FF. Processor B shows 21.
40 (28)
ROM
Follow the general instructions for faults. See
General Instructions for Faults on page 39
50 (32)
CASE
51 (33)
RAM
52 (34)
Flow control
53 (35)
Unused interrupt
54 (36)
Stack
55 (37)
Wrong revision number (Processor B only)
56 (38)
Array overflow
57 (39)
ADC
58 (40)
Input not equal to other processor
Table 16 - GLT Relay Nonrecoverable Fault Codes
Fault Code
Decimal (Hex)
Description
Recommended Action
Содержание Guardmaster 440R-ENETR
Страница 12: ...12 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 1 Product Overview Notes...
Страница 62: ...62 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 6 AOP ControllerTags Notes...
Страница 76: ...76 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 9 Explicit Communication Notes...
Страница 78: ...78 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix A Specifications Notes...
Страница 80: ...80 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix B Regulatory Approvals Notes...
Страница 84: ...84 Rockwell Automation Publication 440R UM009C EN P July 2019 Index Notes...
Страница 85: ......