Rockwell Automation Publication 440R-UM009C-EN-P - July 2019
13
Chapter
2
Installation
Relay Arrangement
shows a typical setup. The ENETR interface must be at the leftmost
position. Up to a maximum of six GSR safety relays can be mounted to the right
of the ENETR interface. When OLink 3.x devices (for example, Guardmaster
DG safety relays) are used, they must be located next to the ENETR interface.
The other OLink 2.0 relays can be mounted in any order. The DG safety relay has
both OLink 2.0 and 3.x, so it can pass information from OLink 2.0 devices to the
ENETR interface.
Figure 2 - Typical Arrangement of ENETR Interface and GSR Relays
Mount on DIN Rail
Follow these steps to mount the ENETR interface on a DIN rail.
1.
Position the adapter vertically above an IEC standard (35x7.5x1 mm
[1.38x0.3x0.04 in.]) DIN rail at a slight angle (DIN rail catalog number
199-DR1; 46277-3).
2.
Press down firmly to install the interface on the DIN rail.
To remove your interface from the DIN rail, pry the DIN rail latch downwards
until there is separation from the latch and the DIN rail.
S12 S22 S32 S42
A1 A2 S11 S12
PWR/Fault
IN1
IN2
Logic IN
OUT
L12 L11 Y32 S34
13 14 23 24
S12 S22 S32 S42
A1 A2 S11 S21
X1 X2 X3 X4
13 14 23 24
OUT
IN 1
IN X
Reset
FB
Config/Set
Sel./Save
DG
Reset
Time
OUT X
IN 2
PWR/Fault
0
2
1
3
4
7
6
9
8
5
S12 S22 S32 S42
A1 A2 S11 S21
X1 X2 X3 X4
13 14 23 24
OUT
IN 1
IN X
Reset
FB
Config/Set
Sel./Save
DG
Reset
Time
OUT X
IN 2
PWR/Fault
0
2
1
3
4
7
6
9
8
5
LOGIC
0 1
2
3
4
5
6
7
8
DI
13 14 23 24
A1 A2
LINK2
MS
LNK1
LINK1
LNK2
NS
A
IP
: 192. 168. 1. ABC
B
C
ENETR
S12 S22 S32 S42
A1 A2 S11 S12
PWR/Fault
IN1
IN2
Logic IN
OUT
L12 L11 Y32 S34
34 44 14 24
LOGIC
0 1
2
3
4
5
6
7
8
DIS
34 44 14 24
A1
33 34 43 44
A1 A2 S11 S12
PWR/Fault
Logic IN
OUT
L12 L11 X32
13 14 23 24
EM
13 14 23 24
33 34 43 44
37 38 47 48
A1 A2 B1 B2
PWR/Fault
B1
Logic IN
OUT
L12 L11 X32
17 18 27 28
RANGE
TIME
EMD
0
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
10
9
Max separation between
relays is 5 mm (0.2 in.).
Locate DG safety relays closest
to the ENETR interface
DIN Rail Latch
DIN Rail
Содержание Guardmaster 440R-ENETR
Страница 12: ...12 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 1 Product Overview Notes...
Страница 62: ...62 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 6 AOP ControllerTags Notes...
Страница 76: ...76 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 9 Explicit Communication Notes...
Страница 78: ...78 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix A Specifications Notes...
Страница 80: ...80 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix B Regulatory Approvals Notes...
Страница 84: ...84 Rockwell Automation Publication 440R UM009C EN P July 2019 Index Notes...
Страница 85: ......