Set the IP Address
Figure 6 - Network Address Example
When you use the switches to assign an address and set it to 001, the gateway
address of the ENETR interface is set to 0.0.0.0, and the subnet mask is
255.255.255.0. When you use the switches to assign an address and set it to a
valid number between 002…254, the gateway address of the ENETR interface is
set to 192.168.1.1, and the subnet mask is 255.255.255.0.
Since the IP address is fixed, the ENETR interface does not show up on the
DHCP/BootP Utility. The ENETR interface is listed on RSLinx program when
a compatible driver is selected.
Use BootP/DHCP Server
When received from the factory, the ABC switches are set to 999, and the
ENETR interface is DHCP enabled. If the ENETR interface was previously
assigned an IP address and you want to change it with the BootP/DHCP server,
then set the ENETR interface back to its factory default setting. Set the ABC
switches to 888 and cycle power and then set the ABC switches to 999 and cycle
the power.
The following example uses BootP/DHCP Version 3.02.00. In this example, the
network is 192.168.2.xxx.
1.
Upon opening, the BootP/DHCP server may prompt for a network
interface similar to the window shown in
. This window does not
appear if there is only one network connection available. For this example,
the ‘USB2.0 to Fast Ethernet Adapter’ with IP address 192.168.2.10 is
selected.
Figure 7 - Select the BootP/DHCP Network Interface
B
C
4
3
2
1
0
5
6
7
9
8
4
3
2
1
0
5
6
7
9
8
4
3
2
1
0
5
6
7
9
8
A
TIP
The ENETR interface goes into DHCP mode for any switch settings except
1…254 and 888. Common practice is to set the switches to 999 or 000.
Содержание Guardmaster 440R-ENETR
Страница 12: ...12 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 1 Product Overview Notes...
Страница 62: ...62 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 6 AOP ControllerTags Notes...
Страница 76: ...76 Rockwell Automation Publication 440R UM009C EN P July 2019 Chapter 9 Explicit Communication Notes...
Страница 78: ...78 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix A Specifications Notes...
Страница 80: ...80 Rockwell Automation Publication 440R UM009C EN P July 2019 Appendix B Regulatory Approvals Notes...
Страница 84: ...84 Rockwell Automation Publication 440R UM009C EN P July 2019 Index Notes...
Страница 85: ......