Publication 1771-6.5.132 - June 2000
4-16
Configuring the DeviceNet Network
4.
Select the
Output
tab.
Highlight the RediSTATION as shown above and click on the
AutoMap
button. The mapping of the RediSTATION will appear in
the lower panel.
In this example, the output to the RediSTATION appears in the
PLC-5 processor in file N10, word 1, as the lower byte (bits 0-7).
Recall from chapter 3 that the indicator light is output bit 0.
Therefore, the address for the RediSTATION’s indicator light is:
N10:1.0
5. Note the address assigned to this output in your system.
You
will enter this address in the example ladder logic program.
After mapping the
RediSTATION output
address will appear
here.
File N10,
Word 1
Note:
The destination address is
actually determined by the block
transfer instruction in the ladder
logic. See chapter 6.
Содержание DEVICENET 1771-SDN
Страница 1: ...PLC 5 DeviceNet Scanner Module 1771 SDN User Manual...
Страница 4: ......
Страница 12: ...Publication 1771 6 5 132 June 2000 P 8 About This User Manual...
Страница 16: ...Publication 1771 6 5 132 June 2000 Table of Contents iv...
Страница 28: ...Publication 1771 6 5 132 June 2000 1 12 Before You Begin...
Страница 38: ...Publication 1771 6 5 132 June 2000 2 10 Planning Your Configuration and Data Mapping Your Devices...
Страница 52: ...Publication 1771 6 5 132 June 2000 3 14 Hardware Setup...
Страница 70: ...Publication 1771 6 5 132 June 2000 4 18 Configuring the DeviceNet Network...
Страница 94: ...Publication 1771 6 5 132 June 2000 5 24 Communicating with DeviceNet from Another Network...
Страница 118: ...Publication 1771 6 5 132 June 2000 B 4 Installing and Configuring the ControlNet Communications Driver...
Страница 122: ...Publication 1771 6 5 132 June 2000 C 4 Installing and Configuring the DH Communications Driver...
Страница 132: ...Publication 1771 6 5 132 June 2000 D 10 Data Map Example...
Страница 137: ......
Страница 139: ...PLC 5 DeviceNet Scanner Module User Manual...