Publication 1771-6.5.132 - June 2000
A-2
1785-ENET Module Channel Configuration
2.
Select the
Channel 3A
tab.
3.
Select
Ethernet
as the
Channel Type
.
4.
Uncheck the
BOOTP Enabled
box to disable BOOTP.
5.
Enter the
IP Address
you want to assign to the PLC-5 processor
(e.g., 130.130.130.2).
6. Download
the configuration to the processor, using a
communications driver that was previously configured, (e.g,
ControlNet or DH+). See chapter 6 for examples of downloading
to the PLC-5 using these drivers.
Содержание DEVICENET 1771-SDN
Страница 1: ...PLC 5 DeviceNet Scanner Module 1771 SDN User Manual...
Страница 4: ......
Страница 12: ...Publication 1771 6 5 132 June 2000 P 8 About This User Manual...
Страница 16: ...Publication 1771 6 5 132 June 2000 Table of Contents iv...
Страница 28: ...Publication 1771 6 5 132 June 2000 1 12 Before You Begin...
Страница 38: ...Publication 1771 6 5 132 June 2000 2 10 Planning Your Configuration and Data Mapping Your Devices...
Страница 52: ...Publication 1771 6 5 132 June 2000 3 14 Hardware Setup...
Страница 70: ...Publication 1771 6 5 132 June 2000 4 18 Configuring the DeviceNet Network...
Страница 94: ...Publication 1771 6 5 132 June 2000 5 24 Communicating with DeviceNet from Another Network...
Страница 118: ...Publication 1771 6 5 132 June 2000 B 4 Installing and Configuring the ControlNet Communications Driver...
Страница 122: ...Publication 1771 6 5 132 June 2000 C 4 Installing and Configuring the DH Communications Driver...
Страница 132: ...Publication 1771 6 5 132 June 2000 D 10 Data Map Example...
Страница 137: ......
Страница 139: ...PLC 5 DeviceNet Scanner Module User Manual...