Safety I/O Module and TÜV Requirements
F-5
Configuration of the 1732DS-IBXOBV4 Safety I/O Module and
PLC Program
The safety module must be configured as follows:
Configure the output that is connected to the I/O output cable
assembly for:
•
Dual (bipolar mode)
•
Safety Pulse Test
Configure the input that is connected to the I/O Input cable assembly
as follows:
•
Channel = Single
•
Mode = Pulsed Test Input from test output X
•
Source = Pulsed output from X
ArmorStart Controller - none required
Safety PLC Program – the program must:
•
Force the output contactors to the open state when a safety-
related stop is demanded.
•
Force the output contactors to remain in the open state if the SM
feedback is open after a safety-related stop is executed (see Note
1 and Note 2).
Note 1: The program must inhibit the contactor closure to satisfy safety
category 4 of 13849-1.
Note 2: The SM feedback logic should be implemented only after a safety-
related stop for the Bulletin 280/281 controllers. It should be ignored
during normal operation. One of the series contactors is used for the
normal stop/start function for these controllers. Therefore, a
malfunctioning contactor circuit cannot be distinguished from a normal
running state.
Refer to Publication SAFETY-AT018*, for programming examples.
Содержание ArmorStart Bulletin 280G
Страница 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Страница 2: ......
Страница 18: ...1 8 Product Overview Notes ...
Страница 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Страница 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Страница 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Страница 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Страница 54: ...2 36 Installation and Wiring Notes ...
Страница 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Страница 157: ...Explicit Messaging on DeviceNet 6 7 ...
Страница 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Страница 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Страница 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Страница 210: ...10 22 Troubleshooting Notes ...
Страница 224: ...A 14 Specifications Notes ...
Страница 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Страница 292: ...E 4 Accessories Notes ...
Страница 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Страница 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Страница 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Страница 323: ......