4-26
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.
Parameter Number
133
Related Parameter
155, 158, 161, 189, 190, 198,
214, 218
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 A
Minimum Value
0.0
Maximum Value
Drive rated amps x 2
Default Value
Based on Drive Rating
Minimum Freq
Sets the lowest frequency the drive will output continuously.
Parameter Number
134
Related Parameter
101, 102, 113, 135, 185, 186,
187, 210, 212
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400
Default Value
0.0
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number
135
Related Parameter
101, 102, 113, 134, 135, 178,
185, 186, 187, 211, 213
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
0.1 Hz
Minimum Value
0.0
Maximum Value
400
Default Value
60.0
Start Source
Sets the control scheme used to start the Bulletin 284G ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number
136
Related Parameters
112 and 137
Access Rule
GET/SET
Data Type
UINT
Group
Basic Program
Units
—
Minimum Value
0
Maximum Value
5
Default Value
5
Stop drive before changing this parameter.
Stop drive before changing this parameter.
Содержание ArmorStart Bulletin 280G
Страница 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Страница 2: ......
Страница 18: ...1 8 Product Overview Notes ...
Страница 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Страница 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Страница 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Страница 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Страница 54: ...2 36 Installation and Wiring Notes ...
Страница 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Страница 157: ...Explicit Messaging on DeviceNet 6 7 ...
Страница 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Страница 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Страница 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Страница 210: ...10 22 Troubleshooting Notes ...
Страница 224: ...A 14 Specifications Notes ...
Страница 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Страница 292: ...E 4 Accessories Notes ...
Страница 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Страница 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Страница 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Страница 323: ......