4-32
Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
15
StpLogic Out
Drive enters Step Logic step with Digit 3 of Command Word (Parameters 240…247).
16
Timer Out
Timer has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.
17
Counter Out
Counter has reached value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto Output 2 Level). Use
Parameter 159 or 162 to set threshold.
18
Above PF Ang
Power factor angle has exceeded the value set in Parameter 159 (Opto Out 1 Level) or Parameter 162 (Opto
Output 2 Level). Use Parameter 159 or 162 to set threshold.
19
Anlg In Loss
Analog input loss has occurred. Program parameter 122 (Analog In Los) for desired action when loss occurs
20
ParamControl
Enables the output to be controlled over the network communications by writing to Parameter 159 (Opto Out 1
Level) or Parameter 162 (Opto Output 2 Level) (0 = Off, 1 = ON).
21
NonRec Fault
Value set in Parameter 192 (Auto Rstrt Tries) is exceeded.
22
EM Brk Cntrl
EM Brake is energized. Program Parameter 260 (EM Brk Off Delay) and Parameter 262 (EM Brk On Delay) for
desired action.
159 (Opto Out1 Level)
162 (Opto Out2 Level)
Sets the trip point for the digital output relay if the value of Parameter 158 (Opto
Out1 Sel) or Parameter 161 (Opto Out2 Sel) is 6, 7, 8, 10, 16, 17, 18, or 20.
Parameter Number
159 162
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
—
Minimum Value
0.0
Maximum Value
9999
Default Value
0.0
Options
Description
ATTENTION
!
Parameter 192 (Auto Rstrt Tries) is not enabled. A non-
resettable fault has occurred.
Parameters 158 and 161
Setting
Parameters 159 and 161
Min./Max.
6
0/400 Hz
7
0/180%
8
0/815V
10
0/100%
16
0.1/9999 sec
17
1/9999 counts
18
1/180
°
20
0/1
Opto Out Logic
Determines the logic (Normally Open/N.O. or Normally Closed/N.C.) of the opto
outputs.
Parameter Number
164
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Program Group
Units
1
Minimum Value
0
Maximum Value
3
Default Value
0
Option
Opto Out1 Logic
Opto Out2 Logic
0
N.O. (Normally Open)
N.O. (Normally Open)
1
N.C. (Normally Closed)
N.O. (Normally Open)
2
N.O. (Normally Open)
N.C. (Normally Closed)
3
N.C. (Normally Closed)
N.C. (Normally Closed)
Содержание ArmorStart Bulletin 280G
Страница 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Страница 2: ......
Страница 18: ...1 8 Product Overview Notes ...
Страница 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Страница 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Страница 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Страница 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Страница 54: ...2 36 Installation and Wiring Notes ...
Страница 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Страница 157: ...Explicit Messaging on DeviceNet 6 7 ...
Страница 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Страница 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Страница 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Страница 210: ...10 22 Troubleshooting Notes ...
Страница 224: ...A 14 Specifications Notes ...
Страница 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Страница 292: ...E 4 Accessories Notes ...
Страница 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Страница 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Страница 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Страница 323: ......