I-4
Step Logic, Basic Logic and Timer/Counter Functions
Timer Function
Digital inputs and outputs control the timer function and are
configured with Parameters 151…154 (Digital Inx Sel) set to 18
Timer Start
and 20
Reset Timer
.
Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level Parameters 156 (Relay Out Level),
159 (Opto Out1 Level), and 162 (Opto Out2 Level) are used to set the
desired time in seconds.
Parameters 155 (Relay Out Sel), 158 (Opto Out1 Sel), and 161 (Opto
Out2 Sel) are set to option 16
Timer Out
and cause the output to
change state when the preset level is reached.
Counter Function
Digital inputs and outputs control the counter function and are
configured with Parameters 151…154 (Digital Inx Sel) set to 19
Counter In
and 21
Reset Counter
.
Digital outputs (relay and opto type) define a preset level and indicate
when the level is reached. Level Parameters 156 (Relay Out Level),
159 (Opto Out1 Level), and 162 (Opto Out2 Level) are used to set the
desired count value.
Parameters 155 (Relay Out Sel), 158 (Opto Out1 Sel), and 161 (Opto
Out2 Sel) are set to 17
Counter Out
which causes the output to
change state when the level is reached.
Example
•
A photo eye is used to count packages on a conveyor line.
•
An accumulator holds the packages until five are collected.
•
A diverter arm redirects the group of five packages to a bundling
area.
•
The diverter arm returns to its original position and triggers a
limit switch that resets the counter.
•
Parameters are set to the following options:
•
151 (Digital In1 Sel) set to 19 to select
Counter In
•
152 (Digital In2 Sel) set to 21 to select
Reset Counter
•
155 (Relay Out Sel) set to 17 to select
Counter Out
•
156 (Relay Out Level) set to 5.0 (counts)
Содержание ArmorStart Bulletin 280G
Страница 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Страница 2: ......
Страница 18: ...1 8 Product Overview Notes ...
Страница 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Страница 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Страница 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Страница 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Страница 54: ...2 36 Installation and Wiring Notes ...
Страница 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Страница 157: ...Explicit Messaging on DeviceNet 6 7 ...
Страница 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Страница 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Страница 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Страница 210: ...10 22 Troubleshooting Notes ...
Страница 224: ...A 14 Specifications Notes ...
Страница 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Страница 292: ...E 4 Accessories Notes ...
Страница 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Страница 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Страница 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Страница 323: ......