ArmorStart® ZIP Configuration
8-3
Data Production
In a typical ZIP system, each device on the network automatically
produces IO data using “Change of State” (COS) triggering. The
automatic production of this COS data by an ArmorStart is enabled
by setting Parameter 67 (AutoRun ZIP) to a value of 1 = Enable. Then
COS data will be produced automatically when the global ZIP enable
parameter (Zone Ctrl Enable, Parameter 99) is set to the value of 1 =
Enable. Data production will take place at a rate specified by
Parameter 68 (Zone ProducedEPR). The minimum period between
Change of State productions is determined by the value of Parameter
69 (Zone ProducedPIT)
Data Consumption
In the ArmorStart data from up to 4 other devices can be consumed
for use in the local logic. The 4 devices whose data is to be consumed
are logically referred to by zone number, i.e. zones 1 – 4. To configure
an ArmorStart to consume data from another node on the network, the
node address or “MacId” is placed in the proper “Zone MacId”
parameter (parameters 70-73). For example to configure an
ArmorStart to consume data for zone 1 from node number 11 on the
network, the value 11 is placed in Parameter 70 (Zone #1 MacId).
Not all zones need to be configured to consume data. If the user
wishes to turn off data consumption for a zone, the value 64 is placed
in the Zone MacId parameter for that zone.
The ArmorStart monitors the frequency at which all consumed data is
received in order to determine the health of each zone’s data
connection. The Zone EPR parameters (parameters 86-89) define the
“Expected Packet Rate” for each of the 4 zone connections.
If no consumed data for a zone is received in 4 times the EPR, then
the zone connection times out, and the value of the corresponding
“Zone Health” parameter (parameters 74-77) is set to the value 1 =
Not Healthy. The “Zone Health” status of each zone is also available
for use in DeviceLogix programs.
Mapping Consumed Data to the
DeviceLogix Data Table.
Consumed data for the 4 zones is placed in an 8 byte section of the
DeviceLogix Data Table. Individual bits in this section of the
DeviceLogix Data Table can be used in DeviceLogix programs. The
table below shows the organization of the 8 bytes of the data table
Byte #
Bit Number and Name
0
ZIP 7
ZIP 6
ZIP 5
ZIP 4
ZIP 3
ZIP 2
ZIP 1
ZIP 0
1
ZIP 15
ZIP 14
ZIP 13
ZIP 12
ZIP 11
ZIP 10
ZIP 9
ZIP 8
2
ZIP 23
ZIP 22
ZIP 21
ZIP20
ZIP 19
ZIP 18
ZIP 17
ZIP 16
3
ZIP 31
ZIP 30
ZIP 29
ZIP 28
ZIP 27
ZIP 26
ZIP 25
ZIP 24
4
ZIP 39
ZIP 38
ZIP 37
ZIP 36
ZIP 35
ZIP 34
ZIP 33
ZIP 32
5
ZIP 47
ZIP 46
ZIP 45
ZIP 44
ZIP 43
ZIP 42
ZIP 41
ZIP 40
6
ZIP 55
ZIP 54
ZIP 53
ZIP 52
ZIP 51
ZIP 50
ZIP 49
ZIP 48
7
ZIP 63
ZIP 62
ZIP 61
ZIP 60
ZIP 59
ZIP 58
ZIP 57
ZIP 56
Содержание ArmorStart Bulletin 280G
Страница 1: ...USER MANUAL Bulletin 280G 281G 284G ArmorStart Distributed Motor Controller ...
Страница 2: ......
Страница 18: ...1 8 Product Overview Notes ...
Страница 29: ...Installation and Wiring 2 11 Figure 2 8 Bulletin 1000 ArmorStart ...
Страница 30: ...2 12 Installation and Wiring Figure 2 9 Bulletin 1000 ArmorStart ...
Страница 42: ...2 24 Installation and Wiring Figure 2 20 Bulletin 1000 Safety ArmorStart ...
Страница 43: ...Installation and Wiring 2 25 Figure 2 21 Bulletin 1000 ArmorStart ...
Страница 54: ...2 36 Installation and Wiring Notes ...
Страница 80: ...3 26 Bulletin 280G 281G Programmable Parameters Notes ...
Страница 157: ...Explicit Messaging on DeviceNet 6 7 ...
Страница 161: ...Explicit Messaging on DeviceNet 6 11 Figure 6 5 ControlLogix Example of Ladder Logic Program ...
Страница 162: ...6 12 Explicit Messaging on DeviceNet Notes ...
Страница 209: ...Troubleshooting 10 21 Figure 10 7 Control Voltage Fuse Replacement Control Voltage Fuse ...
Страница 210: ...10 22 Troubleshooting Notes ...
Страница 224: ...A 14 Specifications Notes ...
Страница 250: ...B 26 Bulletin 280G 281G CIP Information Notes ...
Страница 292: ...E 4 Accessories Notes ...
Страница 300: ...F 8 Safety I O Module and TÜV Requirements Notes ...
Страница 321: ...Step Logic Basic Logic and Timer Counter Functions I 7 Notes ...
Страница 322: ...I 8 Step Logic Basic Logic and Timer Counter Functions Notes ...
Страница 323: ......