Rockwell Automation Publication 2198-RM006A-EN-P - December 2020
61
Appendix C Specifications
Table 44 - Kinetix 5300 (230V, three-phase) Input Power Specifications
Attribute
2198-C2030-ERS
2198-C2055-ERS
2198-C2075-ERS
AC input voltage
170…253V rms, three-phase (230V nom)
AC input frequency
47…63 Hz
Main AC input current (rms)
(1)
15.18 A
31.13 A
36.93 A
Max inrush current (0-pk)
7.4 A
14.8 A
14.8 A
Peak AC input current (rms)
41.26 A
73.06 A
86.25 A
Control power input voltage
(2)
21.6…26.4V DC
24V DC nom
Control power input current
(3)
(non-brake motors)
0.9 A
DC
1.7 A
DC
1.7 A
DC
Continuous output current (rms)
19.6 A
40.2 A
47.7 A
Continuous output current (0-pk)
27.7 A
56.9 A
67.5 A
Peak output current (rms)
(4)
61.0 A
108.0 A
127.5 A
Peak output current (0-pk)
86.3 A
152.7 A
180.3 A
Line loss ride through
20 ms
Continuous output power
5.02 kW
10.30 kW
12.22 kW
Internal shunt on
387.5V
Internal shunt off
377.5V
Internal shunt resistor
60
Ω
40
Ω
Internal shunt power
50 W
75 W
Bus undervoltage limit
144V
Bus overvoltage limit
405V
Bus capacitance
1680 µF
2460 µF
3280 µF
Capacitive energy absorption
30.25 J
44.29 J
59.05 J
Efficiency
97%
Short-circuit current rating
200,000 A (rms) symmetrical
(1) Drives are limited to one power cycle per minute.
(2) The cooling fan runs as part of the control power startup routine, when the inverter is enabled, and if the inverter temperature exceeds preset threshold.
(3) For current values when motors include a holding brake, refer to
Kinetix 5300 Servo Drive Control Power Specifications
(4) Peak RMS current allowed for up to 1.0 seconds.