Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Chapter 5 Communication Connections
•
DHCP Client
•
Sockets Client/Server TCP/UDP
Here are some configuration examples based on the limits described in the
table above:
1. The maximum number of drives that can be controlled over EtherNet/IP
is 16. This is due to the maximum limit of TCP Client connections is 16,
and the maximum limit of EtherNet/IP Client connections is also 16.
2. If you have 10 devices controlled over EtherNet/IP, the maximum
number of devices that can be controlled over serial is six. This is due to
the maximum limit of Client connections is 16.
3. The total number of UDP sockets plus TCP Client/Server sockets has a
maximum limit of eight.
Modbus RTU
Modbus is a half-duplex, master-slave communications protocol. The Modbus
network master reads and writes bits and registers. Modbus protocol allows a
single master to communicate with a maximum of 247 slave devices. Micro800
controllers support Modbus RTU Master and Modbus RTU Slave protocol. For
more information on configuring your Micro800 controller for Modbus
protocol, see the Connected Components Workbench Online Help. For more
information about the Modbus protocol, see Modbus Protocol Specifications
available from
.
Connection Limits for Micro830/Micro850/Micro870 Controllers
Description
Micro830
Micro850/
Micro870
CIP Connections
Total number of client plus server connections for all ports
16
24
Maximum number of client connections for all ports
15
16
Maximum number of server connections for all ports
16
24
Maximum number of EtherNet/IP connections
Client
–
16
Server
23
Maximum number of USB connections
Client
–
–
Server
15
23
Maximum number of Serial connections
Client
15
16
Server
15
23
TCP Connections
Total number of client plus server connections
–
64
Maximum number for EtherNet/IP
Client
16
Server
16
Maximum number for Modbus TCP
Client
16
Server
16
Maximum number for User Programmable Sockets
8
User Programmable Sockets
Total number of User Programmable Sockets
(any combination of UDP plus TCP Client/Server)
–
8
IMPORTANT
If all client/server connections are fully loaded, performance may be
affected, such as data loss and intermittent delays during communication.
Содержание Allen-Bradley Micro850
Страница 12: ...12 Rockwell Automation Publication 2080 UM002L EN E November 2021 Preface Notes ...
Страница 36: ...36 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 2 About Your Controller Notes ...
Страница 44: ...44 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 3 Install Your Controller Notes ...
Страница 120: ...120 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 7 Motion Control Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 9 Controller Security Notes ...
Страница 184: ...184 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 10 Using microSD Cards Notes ...
Страница 226: ...226 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts 10 Click Finish to complete ...
Страница 248: ...248 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts Notes ...
Страница 262: ...262 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix D User Interrupts Notes ...
Страница 272: ...272 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix E Troubleshooting Notes ...