Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
69
Chapter 5 Communication Connections
5. Set Port State as Enabled or Disabled.
6. To manually set connection speed and duplexity, uncheck the option box
Auto-Negotiate speed and duplexity. Then, set Speed (10 Mbps or 100
Mbps) and Duplexity (Half or Full) values.
7. Click Save Settings to Controller if you would like to save the settings to
your controller.
8. On the device configuration tree, under Ethernet, click Port Diagnostics
to monitor Interface and Media counters. The counters are available and
updated when the controller is in Debug mode.
Validate IP Address
Modules must validate the incoming IP address configuration, whether it is
obtained through explicit configuration or through DHCP.
The following rules must be obeyed when configuring the IP address:
•
The IP address for the module cannot be set to zero, a multicast address,
a broadcast address, or an address on the Class A loopback network
(127.x.x.x).
•
The IP address should not start with zero, and the IP address network ID
should be not zero.
•
The Network mask cannot be set to 255.255.255.255.
•
The Gateway address must be on the same subnet as the IP address that
is being configured.
•
The Name Server address cannot be set to zero, a multicast address, a
broadcast address, or an address on the Class A loopback network
(127.x.x.x).
The valid range of static IPv4 IP address exclude:
•
Broadcast or zero IP (255.255.255.255 or 0.0.0.0)
•
IP address starting with 0 or 127 (0.xxx.xxx.xxx or 127.xxx.xxx.xxx)
•
IP address ending with 0 or 255 (xxx.xxx.xxx.0 or xxx.xxx.xxx.255)
•
IP addresses in range 169.254.xxx.xxx (169.254.0.0 to 169.254.255.255)
•
IP addresses in range 224.0.0.0 to 255.255.255.255
Ethernet Host Name
Micro800 controllers implement unique host names for each controller, to be
used to identify the controller on the network. The default host name is
comprised of two parts: product type and MAC address, separated by a
hyphen. For example: 2080LC50-xxxxxxxxxxxx, where xxxxxxxxxxxx is the
MAC address.
The user can change the host name using the CIP Service Set Attribute Single
when the controller is in Program/Remote Program mode.
Содержание Allen-Bradley Micro850
Страница 12: ...12 Rockwell Automation Publication 2080 UM002L EN E November 2021 Preface Notes ...
Страница 36: ...36 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 2 About Your Controller Notes ...
Страница 44: ...44 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 3 Install Your Controller Notes ...
Страница 120: ...120 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 7 Motion Control Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 9 Controller Security Notes ...
Страница 184: ...184 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 10 Using microSD Cards Notes ...
Страница 226: ...226 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts 10 Click Finish to complete ...
Страница 248: ...248 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts Notes ...
Страница 262: ...262 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix D User Interrupts Notes ...
Страница 272: ...272 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix E Troubleshooting Notes ...