Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
107
Chapter 7 Motion Control
4. Set Homing parameters based on the description in
. Click
Homing.
Axis Start/Stop Velocity
Start/Stop velocity is the initial velocity when an axis starts to move, and the
last velocity before the axis stops moving. Generally, Start/Stop velocity is
configured at some low value, so that it is smaller than most velocity used in
the motion function block.
•
When the target velocity is smaller than Start/Stop velocity, move the
axis immediately at the target velocity.
Table 13 - Homing Parameters
Parameter
Value Range
Homing Direction
Positive (clockwise) or negative (counterclockwise).
Homing Velocity
(1)
(1) The parameter is set as REAL (float) value in Connected Components Workbench. To learn more about conversions and rounding of
REAL values, see
Real Data Resolution on page 108
Range
: 1…100,000 pulse/sec
Default
: 5,000.0 pulse/sec (25.0 mm/sec)
NOTE
: Homing Velocity should not be greater than the maximum velocity.
Homing Acceleration
(1)
Range
: 1…10,000,000 pulse/sec
2
Default
: 5000.0 pulse/sec
2
(25.0 mm/sec
2
)
NOTE
: Homing Acceleration should not be greater than Maximum Acceleration.
Homing Deceleration
(1)
Range
: 1…10,000,000 pulse/sec
2
Default
: 5000.0 pulse/sec
2
(25.0 mm/sec
2
)
NOTE
: Homing Deceleration should not be greater than Maximum Deceleration.
Homing Jerk
(1)
Range
: 0…10,000,000 pulse/sec
3
Default
: 0.0 pulse/sec
3
(0.0 mm/sec
3
)
NOTE
: Homing Jerk should not be greater than Maximum Jerk.
Creep Velocity
(1)
Range
: 1…5,000 pulse/sec
Default
: 1000.0 pulse/sec (5.0 mm/sec)
NOTE
: Homing Creep Velocity should not be greater than Maximum Velocity.
Homing Offset
(1)
Range
: -10731073741824 pulse
Default
: 0.0 pulse (0.0 mm)
Home Switch Input
Enable home switch input by clicking the checkbox.
- Input
Read-only value specifying the input variable for home switch input.
- Active Level
High (default) or Low.
Home Marker Input
Enable the setting of a digital input variable by clicking the checkbox.
- Input
Specify digital input variable for home marker input.
- Active Level
Set the active level for the home switch input as High (default) or Low.
Содержание Allen-Bradley Micro850
Страница 12: ...12 Rockwell Automation Publication 2080 UM002L EN E November 2021 Preface Notes ...
Страница 36: ...36 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 2 About Your Controller Notes ...
Страница 44: ...44 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 3 Install Your Controller Notes ...
Страница 120: ...120 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 7 Motion Control Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 9 Controller Security Notes ...
Страница 184: ...184 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 10 Using microSD Cards Notes ...
Страница 226: ...226 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts 10 Click Finish to complete ...
Страница 248: ...248 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts Notes ...
Страница 262: ...262 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix D User Interrupts Notes ...
Страница 272: ...272 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix E Troubleshooting Notes ...