Appendix E Troubleshooting
0xF2Bz
(2)
Recoverable
Expansion I/O configuration fault.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Correct the expansion IO module configuration in the user program to match that of
the actual hardware configuration.
• Check the expansion I/O module operation and condition.
• Replace the expansion I/O module.
0xF300
Recoverable
The memory module is present but memory module
is empty and restore operation is requested.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Check to make sure there is a valid project in the memory module.
• Download a user program and use the backup function to the memory module.
0xF301
Recoverable
The memory module’s project is not compatible with
the controller.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Check to make sure there is a user program with a controller that has the correct
controller catalog configured.
• Download a user program and use the backup function to the memory module.
0xF302
Recoverable
The password is mismatched between memory
module and controller. Only applies to Micro820
controller when Remote LCD performs the restore
operation.
This fault does not apply to Micro800 controller
firmware revision 10 and later.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Check to make sure that the user program in the memory module has the correct
password.
• Download a user program with a password and use the backup function to the
memory module.
• Use Connected Components Workbench software to enter the correct password into
the controller and perform the restore operation again.
0xF303
Recoverable
The memory module is not present and restore
operation is requested.
Check to make sure the memory module is present.
0xF0Az
(3)
Recoverable
The plug-in I/O module experienced an error during
operation.
Perform the following:
• Check the condition and operation of the plug-in I/O module.
• See
Corrective Actions for Recoverable Faults on page 270
0xF0Bz
(3)
Recoverable
The plug-in I/O module configuration does not match
the actual I/O configuration detected.
Perform one of the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Correct the plug-in I/O module configuration in the user program to match that of the
actual hardware configuration.
• Check the condition and operation of the plug-in I/O module.
• Replace the plug-in I/O module.
0xF0Dz
(3)
Recoverable
When power was applied to the plug-in I/O module
or the plug-in I/O module was removed, a hardware
error occurred.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 270
2. Correct the plug-in I/O module configuration in the user program.
3. Build and download the program using Connected Components Workbench software.
4. Put the Micro800 controller into Run mode.
0xF0Ez
(3)
Recoverable
The plug-in I/O module configuration does not match
the actual I/O configuration detected.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 270
2. Correct the plug-in I/O module configuration in the user program.
3. Build and download the program using Connected Components Workbench software.
4. Put the Micro800 controller into Run mode.
0xF830
Recoverable
An error occurred in the EII configuration.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Review and change the EII configuration in the Micro800 controller properties.
0xF840
Recoverable
An error occurred in the HSC configuration.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Review and change the EII configuration in the Micro800 controller properties.
0xF850
Recoverable
An error occurred in the STI configuration.
Perform the following:
• See
Corrective Actions for Recoverable Faults on page 270
• Review and change the EII configuration in the Micro800 controller properties.
0xF860
Recoverable
A data overflow occurred.
A data overflow error is generated when the ladder,
structured text, or function block diagram execution
encounters a divide-by-zero.
Perform the following:
1. See
Corrective Actions for Recoverable Faults on page 270
2. Correct the program to ensure that there is no data overflow.
3. Build and download the program using Connected Components Workbench software.
4. Put the Micro800 controller into Run mode.
Table 56 - List of Error Codes for Micro800 controllers (Continued)
Error Code
Fault Type
Description
Recommended Action
Содержание Allen-Bradley Micro850
Страница 12: ...12 Rockwell Automation Publication 2080 UM002L EN E November 2021 Preface Notes ...
Страница 36: ...36 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 2 About Your Controller Notes ...
Страница 44: ...44 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 3 Install Your Controller Notes ...
Страница 120: ...120 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 7 Motion Control Notes ...
Страница 156: ...156 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 9 Controller Security Notes ...
Страница 184: ...184 Rockwell Automation Publication 2080 UM002L EN E November 2021 Chapter 10 Using microSD Cards Notes ...
Страница 226: ...226 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts 10 Click Finish to complete ...
Страница 248: ...248 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix C Quickstarts Notes ...
Страница 262: ...262 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix D User Interrupts Notes ...
Страница 272: ...272 Rockwell Automation Publication 2080 UM002L EN E November 2021 Appendix E Troubleshooting Notes ...