Rockwell Automation Publication 440R-UM010A-EN-P - May 2015
27
Chapter
5
Diagnostic LEDs and Troubleshooting
The GLT has five LED indicators to provide operating status and diagnostic
information.
LEDs During Power-Up
During power-up, the LEDs turn ON and OFF during their self-check process.
The self-check takes about 3 seconds.
LEDs During Normal
Operation
Table 6 - Normal Operation LEDs
LEDs During Diagnostics
Diagnostics are indicated by the flashing of the LED indicators. The PWR/Fault
indicator shows the major fault. The IN1 indicator shows more detail.
The flashing rate pauses and then repeats itself.
LED Indicator
State
Description
PWR/FAULT
Solid Green
Normal operation
Blinking Red
See
for possible faults. Correct fault and cycle
power
Green with Blinking Red
See
for possible faults. Correct fault and press
reset
IN
ON
Input circuits at S12 and S22 are closed
OFF
Input circuits at S12 and S22 are open
51/L61
ON
Gate is locked
OFF
Gate is unlocked
Blinking
Timing cycle has started
LOGIC IN
ON
Logic IN signal at L12 is active
OFF
Logic IN signal at L12 is OFF
OUT
ON
L11 is active and 14/24 are ON
Y32 is ON
OFF
Outputs are OFF
Blinking
Waiting for reset signal or timing cycle has started
IMPORTANT
For accurate diagnostics, always start counting after the first pause. The first
cycle may not be accurate.