Rockwell Automation Publication 440R-UM010A-EN-P - May 2015

Chapter 5

Diagnostic LEDs and Troubleshooting

Table 7 - Diagnostic LEDs

Power/Status LED

Status/Faults

Solid red

An undeclared fault has occurred.
Cycle power to clear the fault and return the GLT to an operational state.

Flashing red 1 time

The GLT is in configuration mode.
When the Logic Switch is set to 0 or 9 and the power is cycled, the PWR/Fault LED 
will blink at a 1X rate. The GLT is in configuration mode. Rotate the switches to the 
desired positions and cycle power.

Green with Flashing red 2 times

The configuration does not agree with the EPROM.
One or more of the rotary switches have changed during operation. The GLT will 
continue to operate, and the switch(es) can be returned to their original position. If 
the outputs are ON, turn the outputs OFF and press reset to clear the fault.

Green with Flashing red 3 times

The connection to terminal B2 has changed. 
The GLT will continue to operate, and the connection can return to its original status. 
If the outputs are ON, turn the outputs OFF and press reset to clear the fault.

Green with Flashing red 4 times

The safety inputs were closed before the delay time expired.
Open the safety input for the full time cycle. Or connect B2 to 24V and reconfigure 
the GLT for retriggerable inputs. 

Green with Flashing red 5 times

The gate appears open when it supposed to be closed and locked.
The IN1 indicator is OFF - input signals are corrupt.
The 51/L61 indicator is ON - gate should be locked.
Possible fault conditions:

Gate is open

Open circuit on S12

Open circuit on S22

Short from S12 to S22

Short from S12 or S22 to +24V DC

Short from S12 or S22 to 24V Common.

Check the voltage at terminals S12 and S22. Both should have 24V DC. 
Correct the fault. Press Reset to clear the flashing red indication. Press Reset again to 
turn the outputs ON. Cycle both input signals (or cycle power) to return the GLT to an 
operational state.

Flashing red 2 times

Upon power up, one or more of the rotary switch settings do not agree the value 
stored in the EEPROM.
Return the switches to their originally configured settings and cycle power or 
reconfigure the GLT.

Flashing red 5 times

IN1 is flashing 12 times.

Short circuit fault on terminal L11 to 24V.

Short circuit fault on terminal L11 to ground.

With OSSD Guardlocking or E-stop function…

Short circuit fault on terminal 51 to ground.

Correct the fault and cycle power to the GLT.

Flashing red 6 times

IN1 is flashing 7 times

Short circuit fault on terminal 14 to ground or

Short circuit fault on terminal 24 to 24V with pulse testing

IN1 is flashing 8 times

Short circuit fault on terminal 24 to ground or 

Short circuit fault on terminal 24 to 24V with pulse testing or 

Short circuit fault from terminal 14 to terminal 24 with pulse testing.

Correct the fault and cycle power to the GLT.

Flashing red 9 times

IN1 is flashing 9 times

Short circuit from terminal 51 to L61

Open circuit on terminal 51 or L61

IN1 is flashing 10 times

Short circuit fault on terminal 51 or L61 to ground or 

Short circuit fault on terminal 51 or L61 to 24V.

Correct the fault and cycle the power to the GLT.

Flashing red 10 times

IN1 is flashing 33 times

The supply voltage exceeded 26.4V DC - Overvoltage

Correct the power supply and cycle the power.

Содержание Allen-Bradley 440R-GL2S2T

Страница 1: ...GLT Guard Locking with Time Delay Safety Relay Catalog Number 440R GL2S2T User Manual Original Instructions...

Страница 2: ...in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations Labels may also b...

Страница 3: ...s the procedures that you use to install wire and troubleshoot your controller This manual explains how to install and wire your safety relay gives an overview of the GLT safety relay performance Addi...

Страница 4: ...in the open position Reaction Time Describes the time between the true states of one input to the ON state of the output Recovery Time Describes the time that is required for the input to be in the LO...

Страница 5: ...Excessive Heat 11 Chapter3 Power Ground andWiring Wiring Requirements and Recommendation 13 Wire Size 13 Terminal Torque 13 Terminal Assignments 14 Grounding the Controller 14 Connecting a Power Supp...

Страница 6: ...s 31 Pulse Testing of Outputs 31 AppendixA Specifications General 33 Environmental 33 Inputs IN1 34 Lock Unlock Request 34 Retrigger 35 Outputs 35 Lock Unlock Signals 36 Auxiliary Signal 36 Single Wir...

Страница 7: ...When GLT receives a single wire safety signal from other GSR relays the GLT issues an Unlock command When the GLT turns ON its safety output it also turns ON its single wire safety output for use by o...

Страница 8: ...ses must be stopped immediately and some must be stopped shortly thereafter To initiate the stop the operator presses an E stop button The GLT initiates an immediate stop command followed by a delayed...

Страница 9: ...DIN Rail Mounting and Dismounting The GLT easily mounts onto 35 mm DIN Rails 35x7 5x1 mm EN 50022 35x7 5 1 Hold the top at an angle 2 Slide down until the housing catches the rail 3 Swing the bottom d...

Страница 10: ...rial enclosure to reduce the effects of electrical interference and environmental exposure Pollution Degree 2 is an environment where normally only non conductive pollution occurs except that occasion...

Страница 11: ...IEC 60529 as applicable for explanations of the degrees of protection that is provided by different types of enclosure Preventing Excessive Heat For most applications normal convective cooling keeps...

Страница 12: ...12 Rockwell Automation Publication 440R UM010A EN P May 2015 Chapter 2 Installation Notes...

Страница 13: ...t wiring from output wiring Label wiring to all devices in the system Use tape shrink tubing or other dependable means for labeling purposes In addition to labeling use colored insulation to identify...

Страница 14: ...1 S21 Safety Test Pulse Output for Channel 2 S12 Safety Input for Channel 1 S22 Safety Input for Channel 2 S44 Reset and Lock Request Input S54 Guardlocking Unlock Request Input Y32 Auxiliary Nonsafe...

Страница 15: ...devices with mechanical contact outputs such as emergency stop buttons and tongue interlock switches use both a safety input terminal and a test pulse output terminal When safety devices are connecte...

Страница 16: ...nce the TLS3 GD2 has multiple contacts in series the maximum safety performance rating is Cat 3 PLd and SIL CL2 Regardless of how these are wired performance remains the same The GLT successfully reco...

Страница 17: ...L3 Unlock Request Input The Unlock Request Input can be connected to the 24V supply through a momentary normally open push button switch or to a 24V sourcing output of a PLC where the PLC turns the re...

Страница 18: ...nd Unlock Signals The GLT is designed to ignore incidental actuations or stuck conditions on the Lock and Unlock inputs The lock and unlock signals must be actuated for a duration of 0 25 3 seconds Th...

Страница 19: ...input device OFF then ON after the completion of the timing cycle When terminal B2 is connected to 24V DC the safeguarding input device can be closed before the full duration of the timed delay cycle...

Страница 20: ...The 440G MT solenoid cannot be connected directly to the GLT as it draws too much current an interposing relay is required Figure 17 TLS Z and 440G LZ Solenoid Connections When connecting to the TLS Z...

Страница 21: ...e from radiating into adjacent systems The following diagram shows an output with a suppression device We recommend that you locate the suppression device as close as possible to the load device Since...

Страница 22: ...22 Rockwell Automation Publication 440R UM010A EN P May 2015 Chapter 3 Power Ground and Wiring Notes...

Страница 23: ...testing deactivated on terminals 14 24 51 and L61 Function 1 Guardlocking Applications 1 Manual monitored Cat 0 Stop 14 24 L11 Y32 immediate OFF 51 L61 delayed ON Logic IN OR IN1 2 Logic IN AND IN1 3...

Страница 24: ...osition switches with a limited rotation Figure 20 Configuration Switch Adjustment Range Switch Setting Maximum Delay Time Range Switch Setting Maximum Delay Time 0 0 5 s without 10 1 1 To use the Ran...

Страница 25: ...out signals during the configuration process so the wiring must be complete Set the Logic switch to 0 if you want pulse testing active on terminals 14 and 24 9 if you want pulse testing deactivated 2...

Страница 26: ...51 and L61 Table 5 shows the conditions for the OUT LED blink rates Table 5 OUT LED Blink Rates OUT LED Blinks Guardlocking Switch 51 L61 Guardlocking Function E Stop Function 1 time OSSD Guardlocking...

Страница 27: ...nd then repeats itself LED Indicator State Description PWR FAULT Solid Green Normal operation Blinking Red See LEDs During Diagnostics for possible faults Correct fault and cycle power Green with Blin...

Страница 28: ...ate is open Open circuit on S12 Open circuit on S22 Short from S12 to S22 Short from S12 or S22 to 24V DC Short from S12 or S22 to 24V Common Check the voltage at terminals S12 and S22 Both should hav...

Страница 29: ...witches and if necessary report the fault to the factory Table 8 Flash Rate Fault Description Flashes Description 0 No fault 5 S11 Pulse Test Fault 6 S21 Pulse Test Fault 7 OSSD1 Fault Terminal 14 8 O...

Страница 30: ...30 Rockwell Automation Publication 440R UM010A EN P May 2015 Chapter 5 Diagnostic LEDs and Troubleshooting Notes...

Страница 31: ...Figure 22 shows the timings of the two test pulses The pulse on S21 occurs shortly after S11 The pulses are repeated every 15 ms Figure 22 Pulse Test Signals Pulse Testing of Outputs When the GLT conf...

Страница 32: ...est Pattern for E stop Functions Figure 26 shows the pulse test pattern on 51 and L61 when the GLT is configured as two high side outputs The pattern is repeated every 2639 ms Figure 26 Output Pulse T...

Страница 33: ...2 5 mm2 24 14 AWG Wiring Category Copper that withstands 75 C 167 F Terminal Screw Torque 0 4 N m 4 lb in Power Supply Voltage Range 24V DC PELV SELV 0 85 1 1 x rated voltage Power Consumption 2 W Fus...

Страница 34: ...ation I O from Logic No Overvoltage Protection Yes Test Out Pulse Duration 700 s Test Out Pulse Period 17 ms Off Pulse accepted for OSSD setting without declaring the input as OFF Min 0 s Max 700 s Re...

Страница 35: ...of Outputs 4 Output Signals Active High S11 S21 14 and 24 Continuous Output Current 0 5 A Aggregate Current of Outputs per Module Max 1 8 A Surge Output Current Max 1 5 A Surge Output Current Duratio...

Страница 36: ...ort Circuit Protection Yes Output Signals Y32 Continuous Output Current Max 50 mA ON State Voltage Drop P S to Max 0 2V Surge Output Current Max 700 mA Surge Output Current Duration Max 5 ms Load Capa...

Страница 37: ...Duration Max 5 ms Max Load Capacitance 1 F Off State Leakage Current Max 0 1 mA Short Circuit Detection No Short Circuit Protection Yes Galvanic Isolation I O from Logic No Logic 1 4 Logic 5 8 14 24...

Страница 38: ...38 Rockwell Automation Publication 440R UM010A EN P May 2015 Appendix A Specifications Notes...

Страница 39: ...pean Council Directive 2006 42 EC on machinery and the following standards IEC EN 61508 Functional safety of electrical electronic programmable electronic safety related systems IEC EN 62061 Safety of...

Страница 40: ...eet the European Council Directive 2004 108 EC on Electromagnetic Compatibility EMC and the following standards EN 61000 6 4 Generic Standards Emission Standard for Industrial Environments EN 61000 6...

Страница 41: ......

Страница 42: ...Rockwell Automation tests all of its products to help verify that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be ret...

Отзывы: