Rockwell Automation Publication 35-UM001A-EN-P - May 2022
81
Chapter
6
Safety Functions
This chapter only applies to the Armor PowerFlex safety version (35S) used in a
safety application. If you are using an Armor PowerFlex standard version
(35E), this chapter does not apply to you.
The Armor PowerFlex safety version provides hard-wired Safe Torque Off
(STO), integrated Safe Torque Off (STO), integrated drive-based Safe Stop 1
functions, Safe Brake Control (SBC), and integrated controller-based Safe
Monitor functions, capability.
Table 12 - Integrated Safety Functions and Compatible Controllers
Integrated Safety Over the EtherNet/IP Network
Safety Function
Minimum Controller Required
Drive-based stop functions
• Timed Safe Stop 1 (SS1)
• Monitored Safe Stop 1 (SS1)
(1)
• Safe Brake Control (SBC)
(1)
Monitored safety functions require an encoder to be configured in the safety configuration.
• GuardLogix 5580
• Compact GuardLogix 5380
Controller-based stop functions
• Monitored Safe Stop 1 (SS1)
• Safe Brake Control (SBC)
Controller-based monitor functions
• Safely Limited Speed (SLS)
• Safely Limited Position (SLP)
• Safe Direction (SDI)
Safety feedback function
Safety Feedback Interface (SFX)
Integrated STO mode
Safe Torque Off (STO)
Table 13 - Hardwired Safety Functions and Compatible Controllers
Hardwired Safety — No Safety Connection
Safety Function
Minimum Controller Required
for Standard Connection
Hardwired STO mode
Safe Torque Off (STO)
• ControlLogix 5570 or 5580
• Armor ControlLogix 5570
• GuardLogix 5570 or 5580
• Armor GuardLogix 5370
• CompactLogix 5370 or 5580
• Armor CompactLogix 5370
includes GuardLogix variants
• Compact GuardLogix 5370 or 5580
IMPORTANT
The functional safety part of the product does not need any
maintenance (apart from proof testing, if applicable). For the
functional safety part of the product, no spare parts are available
and no repair is possible or intended by the user. If there is a
permanent fault, the device has to be taken out of use and
replaced by another one.