144
Rockwell Automation Publication 35-UM001A-EN-P - May 2022
Chapter 7 Configure the Armor PowerFlex Drive
Perform the following steps to enter your device details.
1. Enter values and use pull-down menus to configure the device definition.
See
Table 56 - Device Definition Settings
Field
Description
Name
Name for your Armor PowerFlex drive
Revision
Firmware revision, including major and minor revision levels
The available major firmware revisions in the pull-down menu are dependent on the AOP
version that is installed.
Description
Optionally add a description of your
Armor PowerFlex drive
Electronic Keying
Exact Match
Indicates that all keying attributes must match to establish
communication. If any attribute does not match precisely, communication
with the device does not occur.
Compatible Module
(default)
Lets the installed device accept the key of the device that is
defined in the project, when the installed device can emulate the
defined device. With Compatible Module, you can typically replace
a device with another device that has the following
characteristics:
• Same catalog number
• Same or higher Major Revision
• Minor Revision as follows:
– If the Major Revision is the same, the Minor Revision must be
the same or higher.
– If the Major Revision is higher, the Minor Revision can be any
number.
Disable Keying
Indicates that the keying attributes are not considered when
attempting to communicate with a device. With Disable Keying,
communication can occur with a device other than the type
specified in the project.
ATTENTION:
Be cautious when using Disable Keying; if used incorrectly,
this option can lead to personal injury or death, property damage, or
economic loss.
We
strongly recommend
that you
do not use
Disable Keying.
If you use Disable Keying, you must take full responsibility for
understanding whether the device being used can fulfill the functional
requirements of the application.
IMPORTANT
Changing Electronic Keying parameters online interrupts
connections to the device and any devices that are connected
through the device. Connections from other controllers can also be
broken. If an I/O connection to a device is interrupted, the result
can be a loss of data.
Connection
Standard Only
(35E or 35S)
An exclusive standard I/O connection that lets the standard input and
standard output connections be configured for Data or Listen Only
connections. The safety input and output connections are set to None.
Safety Only
(35S)
An exclusive safety I/O connection where a programmable controller owns
the communication channel and provides safety data and configuration
from the safety I/O. The standard input and output connections, if
available on the drive, are set to None.
Standard and
Safety
(35S)
There is a data connection and separate safety connection that provides an
exclusive communication channel for standard I/O and safety I/O data.
Ethernet Address
Type the IP address. This setting must match the IP address that you set on the Armor
PowerFlex drive by using one of the methods that are outlined in Set the IP Address on
IP Address
- Enter an IP address, subnet mask, and gateway address for the drive. This
is the IP address that the controller uses to communicate with the drive.
Private Network
- Type or select the desired address. This is the IP address that the
controller uses to communicate with the drive.
Host Name
- Type the host name of the host Ethernet drive.
Safety Instance
Type
Safe Stop Only
STO function and Timed SS1 Safe Stop functions are available.
Single Feedback
Monitoring
Primary feedback is used in the safety object for safe monitoring.
Variant
Standard (E)
Standard drive
Safety (S)
Integrated Safety drive