Chapter 6 Troubleshoot the System
Communication
27
Remote Device /*S:0 Param1*/ is Not Responding
Verify all network connections are correct.
Verify that the communication network cable is connected.
If new ladder logic is downloading to the controller, you could see
this message. After the download, communication should run
normally.
Verify that the network address of the controller matches the
terminal controller address configured in the Communication tab.
In the Communication tab, verify that the protocol specifications are
correct, such as communication rate, data bits, stop bits. These are
all protocol specific.
Communication
28
Invalid Data Address /*S:0 Param1*/
This is not syntactically a valid address.
Communication
30
Bad address in block /*S:0 Param1*/ to /*S:0 Param2*/ on device
/*S:0 Param3*/
This can occur when a write-only address for a controller has been
set for read/write in the external tag of the terminal. Param1 to
Param2 specifies the address block having the issue. Somewhere
within the range is where the write-only address is defined in a
PanelView external tag. Set the external tag to write.
Recipe
1001
Recipe upload started.
This message is for informational purposes. No corrective action
needed.
Recipe
1002
Recipe save failed. Cause: Recipe in Table has not been modified. Make sure that the recipe table is modified before the save operation
is done.
Recipe
1003
Recipe save had errors.
This message is for informational purposes. No corrective action
needed.
Recipe
1004
Recipe save completed successfully.
This message is for informational purposes. No corrective action
needed.
Recipe
1005
Recipe download failed. Cause: Operation canceled.
This message is for informational purposes. No corrective action
needed.
Recipe
1006
Recipe download started.
This message is for informational purposes. No corrective action
needed.
Recipe
1007
Recipe download completed with errors.
This message is for informational purposes. No corrective action
needed.
Recipe
1008
Recipe download completed successfully.
This message is for informational purposes. No corrective action
needed.
Recipe
1009
Recipe Download failed. Cause: Unable to write to /*S:0 Param1*/.
Check for:
Communication errors.
Bad data point specification.
The ingredient value written is outside the Low EU and High EU limits
of the numeric data point assigned. (These are optional OPC defined
properties representing data point minimum and maximum values).
The ingredient value could not be converted to the type of the data
point assigned.
Recipe
1010
Recipe upload completed with errors.
This message is for informational purposes. No corrective action
needed.
Recipe
1011
Recipe upload completed successfully.
This message is for informational purposes. No corrective action
needed.
Recipe
1012
Recipe restore failed. Cause: Operation canceled.
This message is for informational purposes. No corrective action
needed.
Recipe
1013
The status data point for Recipe /*S:0 Param1*/ operation could
not be written to. Data Point= /*S:0 Param2*/
Check for:
Communication errors
Bad status data point specification
The status value written is outside the Low EU and High EU limits of
the numeric data point assigned. (These are optional OPC defined
properties representing data point minimum and maximum values).
The status value could not be converted to the type of the data point
assigned
Recipe
1014
Recipe download failed. Cause: The value /*S:0 Param1*/ is less
than the minimum value /*S:0 Param2*/ allowed for ingredient /
*S:0 Param3*/
Correct the dataset value.
Recipe
1015
Recipe /*S:0 Param1*/ failed. Cause: No Selector on display.
Add a recipe selector device to the screen.
Recipe
1016
Recipe /*S:0 Param1*/ failed. Cause: No DataSet Selector on
display.
Add a dataset selector device to the screen.
Recipe
1017
Recipe /*S:0 Param1*/ failed. Cause: No Table on display.
Add a Recipe Table Panel device to the Screen.
Recipe
1018
Recipe /*S:0 Param1*/ operation was not started because the
system is currently busy performing another Recipe operation.
Wait for a recipe operation to complete before starting the next
recipe operation.
PanelView 800 Terminal Alerts (Continued)
Category
ID
Description
Corrective Action
Содержание Allen-Bradley 2711R-T10T
Страница 8: ...8 Rockwell Automation Publication 2711R UM001H EN E April 2021 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 1 Overview Notes...
Страница 44: ...44 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 2 Configure the Terminal Notes...
Страница 94: ...94 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 5 Virtual Network Computing Notes...
Страница 106: ...106 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 6 Troubleshoot the System Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix B Upgrade Firmware Notes...
Страница 122: ...122 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix C Install and Replace Components Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001H EN E April 2021 Index Notes...
Страница 157: ...Rockwell Automation Publication 2711R UM001H EN E April 2021 157 PanelView 800 HMI Terminals User Manual...