Chapter 6 Troubleshoot the System
Alert
2056
Cannot copy recipe to a loaded application.
Unload application and try again.
Alert
2057
Terminal is running low on application memory
(<Available_Virtual_Memory>bytes).
Reset the terminal or this may lead to fatal error.
Alert
2058
Failed setting property: /*S:0 Param1*/::/*S:0 Param2*/, value =
/*S:0 Param3*/
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
entry). Make sure that the values of the state based objects that write
to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Make sure the Ethernet port is enabled.
Alert
2059
Failed setting property (/*S:0 Param1*/): /*S:0 Param2*/::/*S:0
Param3*/, value = /*S:0 Param4*/
Verify the range of the numeric display that uses the external tag as
its write tag is within the range of a tag (validation should provide a
warning if the range of the tag is greater than the range of a numeric
entry). Make sure that the values of the state based objects that write
to an external tag are within the range of the tag. Make sure that the
value that written to an external tag matches the tag type (for
example, do not write a non-numeric string into a numeric tag).
Alert
2060
Terminal is running low on RAM (<Available_RAM>bytes).
Reset the terminal or this may lead to fatal error.
Alert
2061
Out of memory: Terminal cannot continue to run and will be reset.
This is a out of memory critical message. Dismissing this dialog
causes the terminal to reset.
After the terminal resets, try to edit an application and reduce its size
by removing some objects, for example, user controls, screens, tags,
or alarms.
Alert
2062
Cannot copy recipe to a loaded application.
Unload application and try again.
Alert
2064
Cannot enter Safe Mode while terminal security is enabled.
Disable terminal security and try again.
Alert
2065
Table has changed. Do you want to continue?
Press Yes to continue with the changed Recipe table.
Alert
2066
Logging Error
Make sure a microSD card or USB device is connected to the terminal
to store the datalog.
Alert
2067
Invalid filename
Make sure filename is valid.
Alert
2068
Only one Trend with data logging is allow
Make sure the application only has one Trend with data logging.
Alert
2069
Landscape Orientation. Confirm Restart?
Select No to restart later.
Alert
2070
Portrait Orientation. Confirm Restart?
Select No to restart later.
Alert
2071
Application was designed for a different Orientation and may not
appear or operate as intended. Continue?
Press Yes to continue, or No to cancel. Then change the orientation
of the application in Connected Components Workbench software to
match the terminal and try again.
Alert
2072
Application was designed for a different Platform type and
Orientation, and may not appear or operate as intended.
Continue?
Press Yes to continue, or No to cancel. Then change the catalog of
the application in Connected Components Workbench software to
match the terminal and try again.
Alert
2073
Non-validated application is not supported for CompactLogix
controller. Validate before loading
Validate the application and correct any validation errors, save the
application, then try again.
Alert
2074
Terminal encountered an exception and will reboot
This message is for informational purposes. No corrective action
needed.
Alert
2075
Application will be unloaded. Confirm (Y/N)?
Press Yes to unload the application.
Alert
2076
This application does not have at least one Goto Config button. Set
as Startup Application?
Press Yes to continue setting the application as a startup application,
or No to cancel. Edit the application and make sure there is at least
one Goto Config button.
Alert
2077
Controller Settings cannot be changed for running application.
Stop the application and try again.
Alert
2078
Controller address cannot conflict with PanelView 800 terminal
Station Address.
Make sure the controller address is different from the PanelView 800
terminal station address.
Alert
2079
CompactLogix controller based application must contain valid
path.
Make sure a valid path exists and try again.
Alert
2080
Invalid View-Only password. Password should not contain any
special character.
Make sure the View-Only password does not contain any special
characters.
Alert
2081
Old password does not match with terminal.
Make sure the correct password is entered in the Old Password field.
Alert
2082
VNC Server error.
Restart the terminal and try again.
Alert
2083
Controller address cannot be larger than PanelView 800 terminal
Max Node('31').
Make sure the address of the controller is smaller than the maximum
node of PanelView 800 terminal(’31’).
Alert
2084
Password cannot be empty.
Enter valid password.
Alert
2085
Enable Ethernet port. Confirm Restart?
Press Yes to restart the terminal.
Alert
2086
Disable Ethernet port. Confirm Restart?
Press Yes to restart the terminal.
PanelView 800 Terminal Alerts (Continued)
Category
ID
Description
Corrective Action
Содержание Allen-Bradley 2711R-T10T
Страница 8: ...8 Rockwell Automation Publication 2711R UM001H EN E April 2021 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 1 Overview Notes...
Страница 44: ...44 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 2 Configure the Terminal Notes...
Страница 94: ...94 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 5 Virtual Network Computing Notes...
Страница 106: ...106 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 6 Troubleshoot the System Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix B Upgrade Firmware Notes...
Страница 122: ...122 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix C Install and Replace Components Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001H EN E April 2021 Index Notes...
Страница 157: ...Rockwell Automation Publication 2711R UM001H EN E April 2021 157 PanelView 800 HMI Terminals User Manual...