134
Rockwell Automation Publication 2711R-UM001H-EN-E - April 2021
Appendix E Using PanelView 800 Terminals with CompactLogix 5370 Controllers
Addressing Formats from PanelView 800 Terminals to CompactLogix
5370 Controllers
When mapping a PanelView 800 terminal tag to a CompactLogix 5370
controller tag, make sure you copy the exact name and format of the controller
tag into the address field of the terminal tag in the Tag Editor.
Element Level Addressing
PanelView 800
Data Type
CompactLogix 5370
Data Type
Controller Tag Address
(Global) Example
Controller Tag Address
(Local, MainProgram) Example
Boolean
BOOL
Tag1
Program: MainProgram.Tag1
32-bit integer
DINT
Tag2
Program: MainProgram.Tag2
16-bit integer
INT
Tag3
Program: MainProgram.Tag3
8-bit integer
SINT
Tag4
Program: MainProgram.Tag4
Real
REAL
Tag5
Program: MainProgram.Tag5
String
STRING
*
(1)
*
(2)
(1) Tag6.Data/N – N is the length of String.
(2) Program: MainProgram.Tag6.Data/N
Note the following:
• Tag address of Tag6.Len can be read/written for the length of String.
• Tag address of Tag6.Data[characterNo] is to read/write individual character of string by ASCII. For example, Tag6.Data[1] refers to the element 1.
Accessing a Member of a Structure (predefined, module-defined, user-defined data types)
PanelView 800
Data Type
CompactLogix 5370
Data Type
Controller Tag Address
(Global) Example
Controller Tag Address
(Local, MainProgram) Example
Boolean
BOOL
STRUCTURE.Tag1
Program:MainProgram.STRUCTURE.Tag1
32-bit integer
DINT
STRUCTURE.Tag2
Program:MainProgram.STRUCTURE.Tag2
16-bit integer
INT
STRUCTURE.Tag3
Program:MainProgram.STRUCTURE.Tag3
8-bit integer
SINT
STRUCTURE.Tag4
Program:MainProgram.STRUCTURE.Tag4
Real
REAL
STRUCTURE.Tag5
Program:MainProgram.STRUCTURE.Tag5
String
STRING
*
(1)
*
(2)
(1) STRUCTURE.Tag6.Data/N – N is the length of String.
(2) Program:MainProgram.STRUCTURE.Tag6.Data/N
Boolean Addressing
PanelView 800
Data Type
CompactLogix 5370
Data Type
Controller Tag Address
(Global) Example
Controller Tag Address
(Local, MainProgram) Example
Boolean
DINT
Tag2.bitNo
Program:MainProgram.Tag2.bitNo
Boolean
INT
Tag3.bitNo
Program:MainProgram.Tag3.bitNo
Boolean
SINT
Tag4.bitNo
Program:MainProgram.Tag4.bitNo
bitNo can be any value – 0...31 for DINT, 0...15 for INT and 0...7 for SINT data type tags in CompactLogix 5370 controller.
Array Addressing of an Element
PanelView 800 Data Type CompactLogix 5370 Data Type Controller Tag Address
(Global) Example
Controller Tag Address
(Local, MainProgram) Example
Array Dimensions
Boolean
BOOL
Tag1[x]
Program:MainProgram.Tag1[x]
1
32-bit integer
DINT
Tag2[x,y,z]
Program:MainProgram.Tag2[x,y,z]
1,2,3
16-bit integer
INT
Tag3[x,y,z]
Program:MainProgram.Tag3[x,y,z]
1,2,3
8-bit integer
SINT
Tag4[x,y,z]
Program:MainProgram.Tag4[x,y,z]
1,2,3
Real
REAL
Tag5[x,y,z]
Program:MainProgram.Tag5[x,y,z]
1,2,3
String
STRING
*
(1)
*
(2)
1,2,3
(1) Tag6[x,y,z].Data/N – N is the length of String.
(2) Program:MainProgram.Tag6[x,y,z].Data/N
Содержание Allen-Bradley 2711R-T10T
Страница 8: ...8 Rockwell Automation Publication 2711R UM001H EN E April 2021 Table of Contents Notes...
Страница 16: ...16 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 1 Overview Notes...
Страница 44: ...44 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 2 Configure the Terminal Notes...
Страница 94: ...94 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 5 Virtual Network Computing Notes...
Страница 106: ...106 Rockwell Automation Publication 2711R UM001H EN E April 2021 Chapter 6 Troubleshoot the System Notes...
Страница 118: ...118 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix B Upgrade Firmware Notes...
Страница 122: ...122 Rockwell Automation Publication 2711R UM001H EN E April 2021 Appendix C Install and Replace Components Notes...
Страница 156: ...156 Rockwell Automation Publication 2711R UM001H EN E April 2021 Index Notes...
Страница 157: ...Rockwell Automation Publication 2711R UM001H EN E April 2021 157 PanelView 800 HMI Terminals User Manual...