Chapter 2 Prepare for Installation
Location Planning
When choosing the installation location for your product, make sure that the
location meets the following requirements:
•
Allows the product to be installed in a vertical orientation as shown in the
drawings.
•
Provides a flat and level mounting surface, allowing the product to make
full contact with the mounting surface and stay stable.
•
Allows the bays to be square, and not deformed in any way.
•
Provides a mounting surface that can support the weight of the product.
See
Approximate Weights on page 31
•
Does not expose the product to environmental conditions that are
inconsistent with the
•
Provides sufficient space for the product given its dimensions, required
clearances, and access requirements. These topics are covered in the
following sections:
-
Approximate Dimensions on page 29
-
-
Airflow Clearances and Considerations on page 37
-
Service Cart Access Requirements on page 39
Also consider the following when choosing the installation location for your
product:
•
Ventilation and air conditioning concerns beyond meeting the ambient
temperature requirements
•
Input power cable entry points
•
Motor cable exit points
•
Alignment with other equipment
•
Future needs
Environmental Specifications
The installation site must be compatible with the degree of protection that is
provided by the bay. PowerFlex 755T products are only intended for indoor use.
Category
Specifications
Ambient operation
temperature
IP21, UL Type 1: -20…+40 °C (-4…+104 °F) Frames 8 and 9, All Ratings
IP54, UL Type 12: -20…+40 °C (-4…+104 °F) Frames 8 and 9, All Ratings
Storage temperature
-40…+70 °C (-40…+158 °F)
Relative humidity
5…95% noncondensing
Pollution degree
Pollution Degree 2 per UL61800-5-1.
Shock (acceleration)
The configured bays have the same shock specifications as the 755T drive bays.
Operating shock
Cabinet packaged products – 10 g peak for 11 ms duration (±1.0 ms), three shocks in each
direction in each axis
Packaged for shipment
shock
Meets ASTM International standards
Vibration
The configured bays have the same vibration specifications as the 755T drive bays.
Operating vibration
Cabinet packaged products – 1.000 mm (0.040 in.) displacement, 1 g peak
Packaged for shipment
vibration
Meets ASTM International standards