Rockwell Automation Publication 440R-UM013F-EN-P - July 2021
Chapter 4 Configuration
shows an example of the blinking patterns for the EMD
expansion safety relay. The indicators flash for 0.5 seconds to indicate
the switch settings. The number of flashes is equal to the switch
setting. The blinking pattern repeats after a 2 second pause.
Figure 27 - EMD Expansion Safety Relay Status Indicators Flashing in Configuration Mode
5. Cycle the power to store the settings.
After power-up, the current switch settings are compared to the values
in the EEPROM (makes sure that the switches were not changed while
power was off), and the input and output circuits are checked. Upon
successful completion of the internal checks, the relays are ready for
operation.
Table 8 - Configuration Confirmation
Safety Relay
Status Indicator
Switch Setting
CI
IN
Reset
DI
IN 1
Logic
DIS
IN 1
Logic
EMD
B1
Range
Logic IN
Time
SI
IN
Reset
IMPORTANT
To keep your GSR safety relay from permanently faulting, complete the
configuration process by cycling the relay power within 5 minutes of
rotary switch configuration.
B1 - Indicates that the RANGE Switch is set to 3.
Logic IN - Indicates that the TIME Switch is set to 4
2 s
Pause
0.5 s
Flash
Содержание 440R-D22R2
Страница 12: ...12 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 1 Overview Notes...
Страница 16: ...16 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 2 Installation Notes...
Страница 81: ...Rockwell Automation Publication 440R UM013F EN P July 2021 81 Appendix A Specifications Notes...
Страница 82: ...82 Rockwell Automation Publication 440R UM013F EN P July 2021 Appendix A Specifications...
Страница 89: ...Rockwell Automation Publication 440R UM013F EN P July 2021 89 Guardmaster Safety Relays User Manual...