![Rockwell Automation 440R-D22R2 Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/rockwell-automation/440r-d22r2/440r-d22r2_user-manual_1475786084.webp)
84
Rockwell Automation Publication 440R-UM013F-EN-P - July 2021
Appendix B Regulatory Approvals
Specifications are applicable only if the safety function is demanded at least
once within six months. All diagnostic tests are conducted at least before next
demand. At mission time (TM), the proof test interval (PTI) is assumed.
Components failure rates are according to SN29500.
SIL Rating
Safety relays meet the requirements in
in accordance with
IEC/EN 61508 and IEC 62061.
Performance Level/Category
Safety relays can be used in safety systems that meet up to Category 4 and
Performance Level PLe in accordance with ISO 13849-1.
Table 19 - SIL Rating
440R-S13R2
(CI)
440R-D22R2
(DI)
440R-D22S2
(DIS)
440R-EM4R2
(EM)
440R-EM4R2D
(EMD)
440R-S12R2
(SI)
PFHd (1/h)
4.39 E-09
4.49 E-09
4.39 E-09
1.52 E-09
4.55 E-09
3.98 E-09
Safety Integrity Level Claim
Limit
3
Mode of Operation
High demand
Hardware Fault Tolerance
1
Safe Failure Fraction
99%
Table 20 - Performance Level/Category
440R-S13R2
(CI)
440R-D22R2
(DI)
440R-D22S2
(DIS)
440R-EM4R2
(EM)
440R-EM4R2D
(EMD)
440R-S12R2
(SI)
MTTFd
164
355
484
190
165
262
Category
Up to 4
Performance Level
Up to e
DC avg
99%
Mission Time
20 years
Days of Operation
365 days
Hours of Operation
24 hr
T cycle
8 hr / 8.28 s
Содержание 440R-D22R2
Страница 12: ...12 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 1 Overview Notes...
Страница 16: ...16 Rockwell Automation Publication 440R UM013F EN P July 2021 Chapter 2 Installation Notes...
Страница 81: ...Rockwell Automation Publication 440R UM013F EN P July 2021 81 Appendix A Specifications Notes...
Страница 82: ...82 Rockwell Automation Publication 440R UM013F EN P July 2021 Appendix A Specifications...
Страница 89: ...Rockwell Automation Publication 440R UM013F EN P July 2021 89 Guardmaster Safety Relays User Manual...