Rockwell Automation Publication 1606-RM028A-EN-P - September 2021
5
AC Input
Attributes
Values
Notes
Input voltage
Nom
AC 100…240V
Suitable for TN, TT, and IT mains networks
Input voltage range
—
90…264V AC
Continuous operation
—
85…90V AC
<55 °C (131 °F) ambient temperature
continuously allowed
>55 °C (131 °F) ambient temperature short term
or with output derating, see
—
60…85V AC
Full power for up to 200 ms
—
0…85V AC
No damage to the unit
—
264…300V AC
<500 ms
Allowed voltage L or N to earth Max
300V AC
Continuous, IEC 62103
Input frequency
Nom
50…60Hz
±6%
Turn-on voltage
Typ
80V AC
Steady-state value, load independent, see
Shut-down voltage
Typ
74V AC
Steady-state value, load independent, see
External input protection
—
See
External Input Protection on page 24
Attributes
Values
Notes
AC 100V
AC 120V
AC 230V
Input current
Typ
10.5 A
8.6 A
4.5 A
At 48V, 20 A, see
Power factor
(1)
(1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
Typ
0.99
0.99
0.99
At 48V, 20 A, see
Crest factor
(2)
(2) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Typ
1.47
1.53
1.56
At 48V, 20 A
Startup delay
Typ
800 ms
750 ms
700 ms
See
Rise time
Typ
16 ms
16 ms
16 ms
At 48V, 20 A, resistive load, 0 mF, see
Typ
55 ms
55 ms
55 ms
At 48V, 20 A, resistive load, 20 mF, see
Turn-on overshoot
Max
100 mV
100 mV
100 mV
See
Figure 2 - Input Voltage Range
Figure 3 - Turn-on Behavior, Definitions
Figure 4 - Input Current Versus Output Load at 48V
Figure 5 - Power Factor Versus Output Load at 48V
Turn-on
85
Rated Input Range
V
IN
P
OUT
74
264V AC
Shut
-down
80
Start-up
Delay
Rise
Time
Ov
ershoot
- 5%
Output
Voltage
Input
Voltage
20 A
2
4
6
8
10
12
14
16
18
0
2
4
6
8
10
12 A
Input Current, Typ
A: 100 V AC
B: 120 V AC
C: 230 V AC
A
B
C
Output Current
Power Factor, Typ
2
4
6
8
10
12
14
16
18 20 A
0.75
0.8
0.85
0.9
0.95
1.0
Output Current
A: 100V AC
B: 120V AC
C: 230V AC
A
B
C