14
Rockwell Automation Publication 1606-RM028A-EN-P - September 2021
Electromagnetic
Compatibility
The power supply unit is suitable for applications in an industrial environment
and in a residential, commercial, and light industry environment without any
restrictions.
Attribute
Values
Notes
AC 100V
AC 120V
AC 230V
MTBF SN 29500, IEC 61709
491,000 hr
481,000 hr
537,000 hr
At 48V, 20 A and 25 °C (77 °F)
274,000 hr
269,000 hr
300,000 hr
At 48V, 20 A and 40 °C (104 °F)
MTBF MIL HDBK 217F
Ground Benign
170,000 hr
171,000 hr
183,000 hr
At 48V, 20 A and 25 °C (77 °F);
Ground Benign GB25
126,000 hr
127,000 hr
137,000 hr
At 48V, 20 A and 40 °C (104 °F);
Ground Benign GB40
MTBF MIL HDBK 217F
Ground Fixed
36,000 hr
36,000 hr
39,000 hr
At 48V, 20 A and 25 °C (77 °F);
Ground Fixed GF25
27,000 hr
27,000 hr
30,000 hr
At 48V, 20 A and 40 °C (104 °F);
Ground Fixed GF40
EMC Immunity According to Generic Standards EN 61000-6-1 and EN 61000-6-2
Attributes
Standards
Values
Criteria
(1)
(1) Criterion A: Power supply shows normal operation behavior within the defined limits.
Criterion B: Output voltage dips between 48…42V for 5 ms.
Criterion C: Temporary loss of function is possible. The power supply unit can automatically shut down and restart
without damage or hazards to itself.
Electrostatic discharge
EN 61000-4-2
Contact discharge
8 kV
Criterion A
Air discharge
15 kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz…2.7 GHz
20V/m
Criterion A
Fast transients (burst)
EN 61000-4-4
Input lines
4 kV
Criterion A
Output lines
2 kV
Criterion A
Signal lines (coupling clamp) 2 kV
Criterion A
Surge voltage on input
EN 61000-4-5
L
N
2 kV
Criterion A
L
PE, N
PE
4 kV
Criterion A
Surge voltage on output
EN 61000-4-5
+
-
1 kV
Criterion A
+ / -
PE
1 kV
Criterion A
Surge voltage on signal lines EN 61000-4-5
DC-OK signal
PE
1 kV
Criterion A
Shut-down input
PE
Not relevant due to wire length
(2)
(2) Do not use longer wires than 30 m (98.42 ft) for the shutdown input or use an additional protection.
Conducted disturbance
EN 61000-4-6
0.15…80 MHz
20V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100V AC
0V AC, 20 ms
Criterion A
40% of 100V AC
40V AC, 200 ms
Criterion C
70% of 100V AC
70V AC, 500 ms
Criterion A
0% of 200V AC
0V AC, 20 ms
Criterion A
40% of 200V AC
80V AC, 200 ms
Criterion A
70% of 200V AC
140V AC, 500 ms Criterion A
Voltage interruptions
EN 61000-4-11
0% of 200V AC (=0V)
5000 ms
Criterion C
Voltage sags
SEMI F47
Dips on the input voltage according to SEMI F47 standard
80% of 120V AC (96V AC)
1000 ms
Criterion A
70% of 120V AC (84V AC)
500 ms
Criterion A
50% of 120V AC (60V AC)
200 ms
Criterion A
Powerful transients
VDE 0160
Over entire load range
750V, 1.3 ms
Criterion B
(3)
(3) Criterion A is fulfilled for output current up to 15 A.