![Rockwell Automation 1606-XLS960F Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/rockwell-automation/1606-xls960f/1606-xls960f_original-instructions-manual_1475727006.webp)
4
Rockwell Automation Publication 1606-RM028A-EN-P - September 2021
•
55 A high peak current for 10 ms, for easy fuse tripping
•
Safe Hiccup
PLUS
overload mode
•
Active PFC (Power Factor Correction)
•
Negligible low-input inrush current surge
•
Full power -25…+60 °C (-13…+140 °F)
•
Current sharing feature for parallel use
•
Remote control of output voltage
•
DC-OK relay contact
•
Shut-down input
•
ATEX and IECEx approved
Specifications
Catalog Numbers
Attributes
Values
Notes
Output voltage
DC 48V
Nominal
Adjustment range
48…54V DC
—
Output current
20…17.8 A
Continuous
30…26.7 A
Short term (4 s)
Output power
960 W
Continuous
1440 W
Short term (4 s)
Output ripple
<150 mVpp
20 Hz…20 MHz
Input voltage
AC 100…240V
-15/+10%
Mains frequency
50…60 Hz
±6%
AC input current
8.6/4.5 A
At 120/230V AC
Power factor
0.99/0.99
At 120/230V AC
AC inrush current
17/11 A peak
At 120/230V AC
Efficiency
93.9/95.0%
At 120/230V AC
Losses
62.4/50.5 W
At 120/230V AC
Temperature range
-25…+70 °C
(-13…+158 °F)
Operational
Derating
24 W/1 °C
(24 W/1.8 °F)
(1)
(1) Between 85…90V AC. See
.
60…70 °C (140…158 °F)
Hold-up time
27/27 ms
At 120/230V AC
Dimensions
125 x 124 x 127 mm
(4.92 x 4.88 x 5 in.)
W x H x D
Weight
1900 g (4.2 lb)
—
Cat. No.
Descriptions
1606-XLS960F
Power supply
(48…54V standard unit)
1606-XLC
Wall mount bracket
1606-XLSBUFFER48
Buffer unit
1606-XLSRED40HF
Redundancy module