Front Side and User
Elements
Figure 26 - Front Side
User Elements
A
Input terminals
(screw terminals)
N, L Line input
…PE (protective earth) input
B
Output terminals
(screw terminals, two pins per pole)
+ Positive output
- Negative (return) output
C
Parallel Use/Single Use selector
Set the jumper to Parallel Use when the power supply units are
connected in parallel to increase the output power. To achieve a
sharing of the load current between the individual units, the Parallel
Use regulates the output voltage in such a manner that the voltage at
no load is approximately 4% higher than at nominal load. See
Use to Increase Output Power on page 24
. A missing jumper is equal to
a Single Use mode.
D
Output voltage potentiometer
Multi-turn potentiometer; open the flap to set the output voltage.
Factory setting is 48V at full output current, Single Use mode.
E
DC-OK status indicator
(green)
Shows on when the voltage on the output terminals is >90% of the
adjusted output voltage.
F
Overload status indicator
(red)
• Shows on when the voltage on the output terminals is <90% of the
adjusted output voltage, or if there is a short circuit in the output.
• Flashes when the shutdown is activated or the unit is switched off
due to over-temperature.
• Input voltage is required.
G
DC-OK relay contact
The DC-OK relay contact is synchronized with the DC-OK status
indicator. See
.
H
Shutdown and Remote Control input
Allows the power supply unit to be shut down; can be activated with a
switch contact or an external voltage. The remote control input allows
for adjustment of the output voltage between 44…54V. See
Remote Control of Output Voltage on page 10
.
QUALITY
N L
Input
AC 200-240V
POWER SUPPLY
1606-XLS
1606-XLS960F
18WM
IND.CONT.EQ.
Shut-
Down
Parallel Use
Single Use
13
14
16
15
DC ok
Allen-Bradley
DC ok
OVL
48-
54V
DC 48V / 20A
+ +
B
A
G
H
C
D
E
F
Indicators (LEDs)
Overload LED
DC-OK LED
DC-OK Contact
Normal mode
OFF
ON
Closed
During BonusPower
OFF
ON
Closed
Overload (Hiccup mode) Flashing
OFF
Open
Output short circuit
Flashing
OFF
Open
Temperature shut-down Flashing
OFF
Open
Active shut-down input Flashing
OFF
Open
No input power
OFF
OFF
Open