14
GAHP-A HT S1
GAHP-A HT S
GAHP-A HT
Maximum operating pressure
bar
4
Maximum condensation water flow rate
l/h
4
Water content inside the apparatus
l
4
Water fitting
TYPE
F
thread
" G
1 1/4
Gas fitting
TYPE
F
thread
" G
3/4
Fume outlet
Diameter (∅)
mm
80
Residual head
Pa
80
Size
width
mm
848 (6)
height
mm
1537 (6)
1281 (6)
depth
mm
1258
Weight
In operation
kg
400
390
GeneRAL InfoRMAtIon
INSTALLATION MODE
B23P, B33, B53P
COOLING FLUID
AMMONIA R717
kg
7
WATER H2O
kg
10
MAXIMUM PRESSURE OF THE COOLING CIRCUIT
bar
35
** in transient operation, lower temperatures are allowed
Notes:
As per EN12309-2 evaluated on actual thermal capacity. For operating conditions
1.
other than nominal, refer to the Design Manual.
For flow rates different from the nominal refer to the Design Manual.
2.
PCI 34.02 MJ/m3 (1013 mbar – 15 ° C).
3.
PCI 46.34 MJ/kg (1013 mbar – 15 ° C).
4.
± 10% depending on power voltage and absorption tolerance of electric motors.
5.
Overall dimensions excluding fumes pipes (see Figure 3.1 Size (Standard ventila-
6.
tion)
→
15, 3.2 Dimensions (low consumption ventilation – S1)
→
15and Figure 3.3
Dimensions (low noise version)
→
16).
As an option, a version for operation down to -30 °C is available.
7.
Sound power values measured according to EN ISO 9614.
8.
PCI 29.25 MJ/m3 (1013 mbar – 15 ° C).
9.
Maximum sound pressure values in free field, with directionality factor 2, obtained
10.
from sound power level in compliance with norm EN ISO 9614.
Maximum sound pressure values measured in free field, direction factor 2, accord-
11.
ing to EN 3744.
table 3�3 – PED data
GAHP-A HT
GAHP-A LT
Ped data
COMPONENTS UNDER
PRESSURE
Generator
l
18,6
Leveling chamber
l
11,5
Evaporator
l
3,7
Cooling volume transformer
l
4,5
Cooling absorber solution
l
6,3
Solution pump
l
3,3
TEST PRESSURE (IN AIR)
bar g
55
SAFETY VALVE PRESSURE CALIBRATION
bar g
35
FILLING RATIO
kg of
NH3/l
0,146
FLUID GROUP
GROUP 1°