Installation, user and maintenance manual
– GAHP-A
51
If the CCP is a
6.
terminal node of the network connect the three coloured wires to
the orange connector "P8", as shown in detail "A" of Figure 6.12 Connection of CCI
to CAN-BUS network
→
52. Observe the terminal markings L, H, GND (on the CCI's
board at the base of the socket "P8") which are given both in Table 6.2 CAN BUS
cables type
→
48 and in the example.
If the CCP is an
7.
intermediate node repeat the operations from step 2 to step 4 for
the other length of CAN bus cable required. Connect the six coloured wires to the
orange connector "P8", following the instruction provided in detail "B" of Figure
6.12 Connection of CCI to CAN-BUS network
→
52. Observe the terminal markings
L, H, GND (on the CCI's board at the base of the socket "P8") which are given both
in Table 6.2 CAN BUS cables type
→
48 and in the example.
Insert the orange connector "P8" with the wires first into the opening prepared in
8.
the cover of the CCI, and then into the appropriate socket on the CCI itself, making
sure it is correctly inserted.
Use the rear cover bolts located near the CAN BUS socket to secure the 4 mm
9.
eyelet (or 2 eyelets) (detail D, Figure 6.11 Connection from CAN BUS to connector
P8
→
51). The cable should be secured against pulling out.
The CCI has jumpers J21: the position of the jumpers, depends if the CCI is an interme-
diate or terminal node, must be as shown in Figure 6.12 Connection of CCI to CAN-BUS
network
→
52.
The CCI is is equipped with a backup battery which, if the power supply fails, is capable
of storing set values in the memory; the backup battery has a service life of around
7 years, after which it is necessary to replace it (by contacting a ROBUR Technical Assist-
ance Centre).
figure 6�11 – Connection from CAN BUS to connector P8
Connection detail of cable CAN BUS.
LeGend
A
Insulating tape to protect board/shield
B
CAN BUS cable wires
C
CAN bus cable shield
D
terminal and screw for fixing