First start-up
Installation, use and maintenance manual – Caldaria Con export
39
5
P06
DHW position holding function
By enabling this function it is possible to keep the DHW diverter valve in the DHW
position for a time equal to the DHW post-circulation (parameter P09), in order to
exploit this heat as well.
0 ÷ 1
0
0 = disabled
1 = enabled
P07
Heating timing
You can set the minimum time in which the burner is kept off once the heating
temperature has reached the setpoint.
0 ÷ 90
36
Value in multiples of 5 s (default 36 x
5 = 180 s)
P08
Post-circulation heating timing
It is possible to set the operating time of the pump, in heating mode, after the main
burner has been switched off due to the intervention of the room thermostat.
0 ÷ 90
36
Value in multiples of 5 s (default 36 x
5 = 180 s)
P09
Post-circulation DHW timing
It is possible to set the operating time of the pump, for the DHW service, after the
setpoint in the DHW buffer tank has been reached.
0 ÷ 90
24
Value in multiples of 5 s (default 24 x
5 = 120 s)
P10
Minimum blower speed adjustment for DHW
It is possible to set the minimum speed of the blower for the DHW service, which
corresponds to the minimum power of the burner during a DHW request (see Figure
5.8
p. 43). The value is preset according to the set power (parameter P00) and the
type of gas (parameter P02).
45 ÷ P11
--
Value in hertz (1 Hz = 30 RPM)
P11
Maximum blower speed adjustment for DHW
It is possible to set the maximum speed of the blower for the DHW service, which
corresponds to the maximum power of the burner during a DHW request (see Figure
5.8
p. 43). The value is preset according to the set power (parameter P00) and the
type of gas (parameter P02).
P10 ÷ 203
--
Value in hertz (1 Hz = 30 RPM)
P12
Minimum blower speed adjustment for heating
It is possible to set the minimum speed of the blower for the heating service, which
corresponds to the minimum power of the burner during a heating request (see
Figure 5.8
p. 43). The value is preset according to the set power (parameter P00)
and the type of gas (parameter P02).
45 ÷ P13
--
Value in hertz (1 Hz = 30 RPM)
P13
Maximum blower speed adjustment for heating
It is possible to set the maximum speed of the blower for the heating service, which
corresponds to the maximum power of the burner during a heating request (see
Figure 5.8
p. 43). The value is preset according to the set power (parameter P00)
and the type of gas (parameter P02).
P12 ÷ 203
--
Value in hertz (1 Hz = 30 RPM)
P14
Starting step adjustment
It is possible to set the blower speed during the start-up phases. The value is preset
according to the set power (parameter P00) and the type of gas (parameter P02).
P10 ÷ 203
--
Value in hertz (1 Hz = 30 RPM)
P15 (1)
Legionella function
WARNING: burn hazard. See Paragraph 5.8
0 ÷ 1
1
0 = disabled
1 = enabled
P16
Setting the climate curve (only with outdoor probe OSND009 connected)
The OSND009 outdoor temperature probe may be connected and acts by auto-
matically changing the outlet temperature according to the measured outdoor
temperature. The extent of the correction depends on the set heating control value
Kd (Figure 5.6
p. 42). The choice of the curve is determined by the maximum outlet
temperature Tm and the minimum outdoor temperature Te, taking into account the
degree of insulation of the building. The values of the outlet temperatures Tm refer to
standard systems 30-80 °C or floor systems 25-45 °C. The type of system can be set
using parameter P03.
0 ÷ 30
25
The numbering of the value corre-
sponds to the 'Kd' curves of the graph
(Figure 5.6
P17
Centralized control function via CS contact
By enabling this parameter you can deactivate specific services when closing the CS
contact (Paragraph 4.4
0 ÷ 1
0
0 = disabled
1 = enabled
P18
0-10 V industrial bus drive enable
The 0-10 V industrial bus input can be enabled or disabled to set burner power or
delivery temperature via the external bus.
0 ÷ 2
0
0 = disabled
1 = temperature control mode
2 = power control mode
P19
Min heating setpoint
It is possible to set the minimum user-adjustable heating temperature.
20 ÷ 40
30
Value in °C
P20
Max heating setpoint
It is possible to set the maximum user-adjustable heating temperature.
40 ÷ 90
80
Value in °C
P21 (1)
Maximum setpoint for DHW
It is possible to set the maximum user-adjustable DHW temperature.
45 ÷ 75
60
Value in °C
P22
Δt delivery-return setpoint
It is possible to set the temperature difference between delivery and return.
0
10 ÷ 40
20
0 = disabled
Value in °C
P23
Modulating pump minimum speed
It is possible to set the minimum speed value of the modulating pump during a
request for space heating operation.
50 ÷ 70
60
Value in percentage
P24
Modulating pump maximum speed
It is possible to set the maximum speed value of the modulating pump during a
request for space heating operation.
70 ÷ 100
100
Value in percentage
P25 (1)
DHW buffer tank setpoint differential
It is possible to set the differential value with respect to the DHW setpoint at which
the DHW buffer tank charge is activated. For example, with the DHW setpoint at 50
°C and the parameter value at 5 °C, DHW buffer tank recharging starts at 45 °C (50-5)
and stops when the storage reaches the DHW setpoint. The parameter is only active if
the buffer tank probe OSND011 is connected.
3 ÷ 9
9
Value in °C