4.
8
Technical Data - Ecoflam 2-Sta
g
e Oil Burners
Model
030
040
050
060
070
080
0100
Maximum Gross Heat Input
(kW)
(Btu/h) x (1000)
93.2
318.0
129.9
443.2
162.0
552.7
208.0
709.7
242.0
825.7
275.2
939.0
348.5
1189.1
Maximum Net Heat Input
(kW)
(Btu/h) x (1000)
84.0
286.6
117.0
399.2
146.0
498.2
187.4
639.4
218.0
743.8
248.0
846.2
314.0
1071.4
Minimum Gross Heat Input
(kW)
(Btu/h) x (1000)
65.2
222.5
90.9
310.2
113.4
386.9
145.6
496.8
169.4
578.0
192.6
657.2
244.0
832.5
Minimum Net Heat Input
(kW)
(Btu/h) x (1000)
58.8
200.6
81.9
279.5
102.2
348.7
131.2
447.7
152.6
520.7
173.6
592.3
219.8
750.0
Maximum Heat Output
(kW)
(Btu/h) x (1000)
77.1
263.0
107.4
366.5
134.5
458.9
171.5
585.2
200.8
685.1
230.4
786.1
289.5
987.8
Minimum Heat Output
(kW)
(Btu/h) x (1000)
55
188
77
263
94
321
124
423
144
491
161
549
205
699
Light Fuel Oil (Gas Oil) Data
Burner Type
MAX 12
MAX 15
MAX 15
MAX 25
MAX 25
MAX 25
MAX 35
Oil Pump Connection
3/8
Nozzle Size
US (gal/h)
1.5
2.25
3
2.75 / 1.5 3.00 / 2.00 3.50 / 2.00 4.50 / 2.50
Angle & Type
60° H
60° B
60° B / 60°
H
60° B
60° B
60° B
Make
Danfoss
Head Setting
number
0.5
0
0
1
1.5
3.5
1.5
Low Air Setting
number
3.8
1.5
1.9
1.6
2.1
1.8
1.5
High Air Setting
number
2
2
2.5
2.5
4.5
5
3
Burner Fuel Pressure
Bar
16 / 10
7 / 15.5
15 / 8
11
11
12
12
lbf/in^2
232.1 /
145.0
101.5 /
224.8
217.6 /
116.0
159.5
159.5
174.0
174.0
Low Fuel Consumption
L/h
7
8.5
12.9
12.7
14.3
17
21.1
UK (gal/h)
1.5
1.9
2.8
2.8
3.1
3.7
4.6
High Fuel Consumption
L/h
8.9
12.4
15.6
20
23.3
26.4
33.5
UK (gal/h)
2.0
2.7
3.4
4.4
5.1
5.8
7.4
Maximum Pressure to Pump inlet
Bar
2
lbf/in^2
2.9
Kerosene Data
Nozzle Size
*US (gal/h)
1.75
3.00
3.50
3.00 / 2.00 3.50 / 2.50 4.00 / 2.50 5.50 / 3.00
Angle & Type
60°EH
60°B
Make
Danfoss
Head Setting
(number)
0.5
0
0
1
1.5
3.5
1.5
Low Air Setting
(number)
3.8
1.5
1.9
1.6
2.1
1.8
1.5
High Air Setting
(number)
2
2
2.5
2.5
4.5
5
3
Burner Fuel Pressure
(Bar)
(lbf/in
2
)
7 / 12
101.5 /
174.0
7 / 9.5
101.5 /
137.8
10
145.0
9.5
137.8
8.5
123.3
10
145.0
8.5
123.3
Low Fuel Consumption
(L/h)
*UK (gal/h)
5.5
1.2
7.2
1.6
9.2
2.0
12.8
2.8
16.1
3.5
20.6
4.5
23.9
5.3
High Fuel Consumption
(L/h)
*UK (gal/h)
9.2
2.0
12.8
2.8
16.1
3.5
20.6
4.5
24.0
5.3
27.2
6.0
34.5
7.6
Содержание Combat MGB0100
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...1 of 85 Product Approval ...
Страница 65: ...SECTION 14 TROUBLESHOOTING 59 of 85 14 3 Troubleshooting for Gas Burners see manufacturer s instructions ...
Страница 91: ...SECTION 16 SPARE PARTS LIST 85 of 85 ...
Страница 92: ......