ANALYTICAL COMPUTER GC 9000
.........................................................................................................................................................................................................
...............................................................................................................................................................................................................
Manual EMC 500 · EN01 · 2008-02
35
Serial Interfaces
7
indirect
Gas Comp.
and once
left
Column J Description of coordinates
Unit
Comment(s)
1
D RS-FRONT
Heading serial interface front panel
2
C Fr-Type
Front port type:
OFF
1)
12
D RS_LPT
Heading serial printer interface C1
13
C C1-Type
Port C1 type:
OFF / Line-PRT
14
C C1-Baud
Port C1 baudrate:
9600 / 19200
21
D RS_C2
Heading serial data interface C2
22
S C2-Type
Port C2 type:
OFF / DSfG
24
S C2-Baud
Port C2 baudrate:
9600 / 19200 / 38400
35
D RS_C3
Heading serial data interface C3
36 S C3-Type
Port
C3
type: OFF / MB-Sl.ASCII / MB-Sl.RTU / RMG bus
37
S C3-Baud
Port C3 baudrate:
9600 / 19200
38
S C3-Bits
Port C3 number of bits:
7 / 8
39
S C3-Pari
Port C3 parity:
None / Even / Odd
40
S C3-Stop
Port C3 stop bits:
1 / 2
41
S C3-Test
Port C3 modbus test
OFF / Mod I-10 UI / Val F-02 FL / No. Y-20 UL /
Sim x-xx DL / Sim R-46 ST / Diagnostics
2)
42
S C3-UI
Port C3 unsigned int transmission:
1234 / 4321
43
S C3-UL
Port C3 unsigned long transmission:
1234 / 4321
44
S C3-FL
Port C3 float transmission:
1234 / 4321
45
S C3-DB
Port C3 double transmission:
1234 / 4321
46
S C3-MbAdd
Port C3 modbus address
47
S C3-Offs
Port C3 modbus register offset
48
D C3-Text
RMG bus reference text
50
D RS_C4
Heading serial data interface C4
51 S C4-Type
Port
C4
type: OFF / MB-Sl.ASCII / MB-Sl.RTU / RMG bus
52
S C4-Baud
Port C4 baudrate:
9600 / 19200
53
S C4-Bits
Port C4 number of bits:
7 / 8
54
S C4-Pari
Port C4 parity:
None / Even / Odd
55
S C4-Stop
Port C4 stop bits:
1 / 2
56
S C4-Test
Port C4 modbus test
OFF / Mod I-10 UI / Val F-02 FL / Nr. Y-20 UL /
Sim x-xx DL / Sim R-46 ST / Diagnostics
2)
57
S C4-UI
Port C4 unsigned int transmission:
1234 / 4321
58
S C4-UL
Port C4 unsigned long transmission:
1234 / 4321
59
S C4-FL
Port C4 float transmission:
1234 / 4321
60
S C4-DB
Port C4 double transmission:
1234 / 4321
61
S C4-MbAdd
Port C4 modbus address
62
S C4-Offs
Port C4 modbus register offset
63
D C4-Text
RMG bus reference text
65
D RS_C5
Heading serial data interface C5
66
S C5-Type
Port C5 type:
OFF / EMC-Master
1) The operation of the front interface is not supported at the moment.
2) On this menu, test values can be transmitted through the Modbus interface. The computer behaves as if
a field of the computer has been questioned by a specific query and then permanently outputs the value
for the appropriate field. It is possible to test the formats unsigned int, float, unsigned long, double,
string and the diagnostics command. In this version of the GC 9000-EMC, the formats double and string
are not available!