Rittal Liquid Cooling Package
53
9 Operation
EN
Fig. 67:
Layout of screen pages
Key
1
General information
2
Tree view of overall system
3
Main section with index tabs
4
Message display
9.4.2
Selection tree in left-hand section
The overall system including all installed components
is displayed in the form of a tree structure in the left-
hand section of the screen.
At the top of the tree is the processing unit, i.e. the
overall system. Below the overall system is the sub-
group Real Devices. The CMC III PU, the Liquid
Cooling Package itself and all devices and sensors in-
stalled as hardware are listed in this group (see as-
sembly and operating instructions for the CMC III PU).
Each device can assume different statuses. To allow
rapid identification of the current status, the symbol
before the respective device is colour-coded:
Tab. 6: Status display symbols
9.4.3
Index tabs in the right-hand section
Four index tabs are displayed in the right-hand sec-
tion of the screen:
1. Observation: Current data of the Liquid Cooling
Package or connected devices (see section 9.5
"Observation index tab").
2. Configuration: Configuration of basic settings (see
section 9.6 "Configuration index tab").
3. Logging: Message archive about the Liquid
Cooling Package and connected devices (see as-
sembly and operating instructions for the
CMC III PU).
4. Tasks: Creating links between different values and
related actions (see section 9.7 "Tasks")
The content of the index tabs
Observation
and
Con-
figuration
depends on whether the entire system
("Processing Unit" entry) or an individual component,
e.g. "Liquid Cooling Package" entry has been select-
ed in the left-hand section of the screen.
9.4.4
Message display
Current pending messages are displayed in the bot-
tom section of the screen. The message display is
structured as follows:
1. Timestamp: The date and time when the error oc-
curred (fig. 68, item 1).
2. Severity: Severity of the error. A distinction is
made between Warnings and Alarms (fig. 68,
item 2).
3. Message: Error message in plain language
(fig. 68, item 3).
Symbol
Explanation
Status "OK". There are no warnings or alarm
messages.
Status "Warning". There is at least one warn-
ing message.
Status "Alarm". There is at least one alarm
message.
Status "OK". The additional information sym-
bol indicates that further status information
may be displayed. This symbol is only dis-
played if the registered user has at least read-
only access to the data for that particular de-
vice.
Status "Detected". The sensor has recently
been added and not yet confirmed. This sen-
sor must be confirmed by pressing the "C"
button on the CMC III PU or via the Web inter-
face.
Status "Lost". Communication with a sensor is
no longer possible. The connection must be
checked. Alternatively, the sensor can also
be logged off by confirming.
Status "Changed". The sequence of sensors
has been altered and not yet confirmed. This
configuration change must be confirmed by
pressing the "C" button on the CMC III PU or
via the Web interface.
Symbol
Explanation