Arriva/Evolve flue installation guide: 10726-I 09-21
The ASPDFK is suitable from walls up to 385 mm thick. For the Arriva models it
can be used as an alternative to the Direct A and B flue kits. The ASPDFK can
be cut to length to suit wall thicknesses less than 385 mm. The ASPDFK can
also be used in combination with ESPIPE900 for walls greater than 385 mm,
this is called direct extended flueing.
IMPORTANT
Refer p.20 if cutting to length for important information about cutting the outer and inner pipes.
Direct flueing using the ASPDFK
1. Create the wall penetration. The minimum diameter is 80 mm to non-combustible surfaces
such as brick, and 100 mm to combustible surfaces such as plaster. Allow for a continuous 2°
fall from the fire to the wall terminal.
2. Slide the internal wall plate over the terminal end of the ASPDFK pipe until it is nested on the
raised ring of the flue transition.
3. Pass the ASPDFK through the internal wall penetration.
4. Slide the internal wall plate so it is flush with the wall.
5. Create the wall terminal, refer p.21.
6. Move the fire into place and connect the fire flue pipe to the flue. This is done with the flue slide
stopper provided with the flue kit.
Interio
r wall
Exterio
r wall
Direct flueing and direct extended flueing
Max. wall thickness 385 mm
Internal wall plate, outer face