4. How to Use
4-4. How to wire
- 19 -
TP-70DGII
Coil
Load
SK1
SK2
Power
supply
Power
supply
Alarm contact
External relay
(low voltage relay)
* SK1, SK2: Surge absorbing parts
4-4. How to wire
<Recommended Cables>
4 - 20 mA transmission
Shielded cable of CVVS, etc. (1.25 sq) - 2-core
Contact output
Cable of CVV, etc. (1.25sq) - max. 6-core
2-wire type DC power-line
communication system
Shielded twisted-pair cable of KPEV-S, etc. (1.25 sq) - 1P
LAN (for Ethernet and PoE)
Ethernet cable (category 5 or higher)
UTP (unshielded twisted-pair cable)
Supported medium type: 100BASE-T or higher
Cable specification: Single wire (5 m maximum for a
stranded wire)
Modular plug: RJ-45
Number of cores: 8-core
Wire connection: Straight
<Figure of Terminal Plate>
1 2 3 4 5 6 7 8 9 10
+
-
+
-
24 VDC
4-20mA
ALM1
contact
ALM2
contact
FAULT
contact
1 2 3
L N FG
AC IN
CAUTION
Be careful not to damage the internal electronic circuit when wiring. In addition, be careful not to
apply stresses on the gas detector when (overweight) cables are installed.
The power cables and signal cables must not be installed together with the motor power cables,
etc. When these cables must be installed together for unavoidable reasons, put the power cables
and signal cables in a metal conduit. The conduit must be connected to a grounding circuit.