20095002
60
GB
Faults - Probable causes - Solutions
110
#
Voltage monitoring test internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
111
0
Low level of power supply
Insufficient mains voltage.
Conversion of the diagnostic code ---> Voltage value
(230 V AC : 1,683)
112
0
Reset power supply voltage
Error code for the carrying out of a reset in the event of power
supply restoration (absence of error)
113
#
Mains voltage supervision internal error
Carry out a reset; if the error arises repeatedly, replace the
control box
115
#
Control box meter internal error
116
0
Life cycle of the control box in the critical interval
(250,000 Start ups)
The envisaged life cycle of the control box has been exceeded.
Replace it.
117
0
Life cycle of the control box exceeded
The switch-off threshold has been reached.
120
0
Interruption of fuel limiting meter input
Too many disturbance impulses on the input of the fuel meter -
--> Improve the electromagnetic compatibility.
121 ÷ 124
#
EEPROM access internal error
Carry out a reset, repeat and check the last setting of the
parameters. Restore the group of parameters: if the error arises
repeatedly, replace the control box.
125
#
EEPROM reading access internal error
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
126
#
EEPROM writing access internal error
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
127
#
EEPROM access internal error
Carry out a reset, repeat and check the last setting of the
parameters. Restore the group of parameters: if the error arises
repeatedly, replace the control box.
128
0
EEPROM access internal error - synchronisation
during the initialisation
Carry out a reset; If the error arises repeatedly, replace the
control box.
129
#
EEPROM access internal error – command
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
130
#
EEPROM access internal error - time-out
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
131
#
EEPROM access internal error - page interrupted
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
132
#
EEPROM register initialisation internal error
Carry out a reset; If the error arises repeatedly, replace the
control box.
133 ÷ 135
#
EEPROM access internal error – request
synchronisation
Carry out a reset, repeat and check the last setting of the
parameters. If the error arises repeatedly, replace the control
box.
136
1
Restoration started
The restoration of a backup has been started (no error)
137
#
Internal error – backup / restoration
157 (-99)
Restoration – OK, but backup < compared with set data of
current system
Restoration successful, but the backup data installed are fewer
than those currently present in the system.
239 (-17)
Backup - logging of the backup on RDI21… failed
Perform the reset and repeat backup
240 (-16)
Reset - no backup in RDI21…
No backup in RDI21…
241 (-15)
Reset - Interruptions relating to impracticable ASN
The backup has an impracticable ASN and cannot reset the
unit
242 (-14)
Backup – the backup carried out is contradictory
The backup is irregular and cannot be transferred again
243 (-13)
Backup – the data comparison between the internal
microprocessors is irregular
Repeat the reset and backup
244 (-12)
The backup data are incompatible
The backup data are incompatible with the current version of
the software; the restoration is not possible
245 (-11)
Error in access to the parameter Restore_Complete
Repeat the reset and backup
246 (-10)
Restoration – time-out during logging in EEPROM
Repeat the reset and backup
247 (-9)
The data received are contradictory
The series of backup data is not valid; restoration is not
possible
248 (-8)
The restoration cannot currently be carried out
Repeat the reset and backup
249 (-7)
Restoration – interruption caused by inadequate
identification of the burner
The backup has an inadequate identification of the burner and
must not be transferred to the control box
250 (-6)
Backup – the CRC of a page is not correct
The series of backup data is not valid; restoration is not
possible
251 (-5)
Backup – the identification of the burner is not defined
Define the identification of the burner and repeat the backup
Error
code
Diagnostic code
Meaning of the REC 27.100A2 system
Recommended measures
Содержание RS 160/EV BLU TC
Страница 2: ...Original instructions...
Страница 69: ...67 20095002 GB Appendix Electrical panel layout 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 67 8 9...
Страница 70: ...20095002 68 GB Appendix Electrical panel layout 0 1 1 0 2 0 00 0 1 3 414 56 2 7 8 03 59 3 A...
Страница 71: ...69 20095002 GB Appendix Electrical panel layout...
Страница 72: ...20095002 70 GB Appendix Electrical panel layout 0 1 1 2 1 1 1 1 1 3 3 3 1 1 0 1 1 4 4 1 4 41 1 1 5 6 4 4 768 9...