Start-up, calibration and operation of the burner
6.6.2
Info mode
The
Info mode
(
InFo
) visualises general system information. To
access this level you must:
press the “
i/reset
” key for 1-3 s.
Release the key immediately when the display shows
“InFo”
.
The list of parameters (in the sequence in which they are dis-
played) is shown in Tab. O.
Tab. O
6.6.3
Service mode
The
Service mode
(
SEr
) visualises the error log and certain
technical information about the system. To access this level you
must:
press the
“i/reset”
key for more than 3 s.
Release the key immediately when the display shows
“SEr”
.
The list of parameters (in the sequence in which they are dis-
played) is shown in Tab. P.
Tab. P
6.6.3.1 Operating mode on Info Mode and Service Mode
After access to these levels, the display visualises the number of
the parameter (flashing) on the left, and the corresponding value
on the right.
If the value is not displayed, press the
“i/reset”
key for 1 to 3 sec-
onds
To return to the Parameter List, press the
“i/reset”
key for more
than 3 s, or press the keys
“+”
and
“-”
(
ESC
) simultaneously.
To move on to the next parameter, press the
“+”
or
“i/reset”
key
for less than 1 s. At the end of the list, the display visualises
“End”
.
To move back to the previous parameter, press the key
“-”
.
To return to the Normal/Standard Visualisation Mode, press the
“i/reset”
key for more than 3 s, or press the keys
“+”
and
“-”
(
ESC
) simultaneously.
For a moment the display will show
“OPErAte”
.
No.
Parameter
167
Volumetric delivery of fuel in the unit of measurement
selected
162
Operation time with flame
163
Operation time
164
No. of resettable ignitions
166
Total no. of ignitions
113
Identification code of the burner
107
Software version
108
Software variation
102
Control box test date
103
Identification code of the control box
104
Identification number of the group of parameters set
105
Version of the group of parameters
143
Reserved
End
/reset
P
%
min
V
h
s
D9019
No.
Parameter
954
Flame intensity (%)
960
Actual fuel which passes in units of volume / h
(m³/h, l/h, ft³/h, gal/h)
121
Manual setting of output
Not defined = automatic operation
922
Position of the servomotors (expressed in de-
grees, symbol
)
0 = fuel
1 = air
161
Number of errors
701÷725
Log of the errors: 701-725.01, Code
/reset
D9020
P
s
h
V
min
%
D9021
P
%
min
h
s
Содержание RS 160/EV BLU TC
Страница 2: ...Original instructions...
Страница 69: ...67 20095002 GB Appendix Electrical panel layout 0 1 2 2 2 3 2 4 2 2 2 2 2 2 2 52 5 5 2 2 3 2 67 8 9...
Страница 70: ...20095002 68 GB Appendix Electrical panel layout 0 1 1 0 2 0 00 0 1 3 414 56 2 7 8 03 59 3 A...
Страница 71: ...69 20095002 GB Appendix Electrical panel layout...
Страница 72: ...20095002 70 GB Appendix Electrical panel layout 0 1 1 2 1 1 1 1 1 3 3 3 1 1 0 1 1 4 4 1 4 41 1 1 5 6 4 4 768 9...