Electrical Specifications
UPS Power Modules (kVA)
10
12
15
20
DC INTERMEDIATE CIRCUIT
Numbers of elements at Pb
120+120
Float voltage
(2,27 V/el., selectable)
273+273 Vdc
Charging voltage
(2,4 V/el., selectable)
288+288 Vdc
End of discharge voltage – load
dependent (1,6 V/el., adjustable)
192+192 Vdc
Standard battery charger
(2)
6 A NOMINAL
Load 100%
Load 95%
Load 90%
4 A
5 A
6 A
4 A
6 A
6 A
Charger
replacement
(2)
See
§
11.5
Replacement 10 A - ONLY MSM
Load 100%
Load 90%
Load 80%
Load 70%
4 A
6 A
8 A
10 A
4 A
7 A
10 A
10 A
(2)
The current refer to input voltages ≥200 Volt