MULTI SENTRY
SPTMSTD2T16EREN
23
Auto system on
Automatic UPS power-on
Disabled
Disable
Enable
UPS Input
Current
UPS input current shown on
display
Disabled
Disable
Enable
Bypass
Synchronisation
speed
Selects the synchronisation
speed of the inverter to the
bypass line
1 Hz/sec
0,5 Hz/sec
1 Hz/sec
1,5 Hz/sec
2 Hz/sec
Panel lock -
Enable config
change
Disables UPS settings from
the Display Panel
Settings
enabled
Settings enabled
Settings disabled
Display Code
Disable the access to display
complete menu (remain
accessible measures, states,
alarms, menu, only)
Disabled
Enable and setup the code sequence
(4 selecting characters, 6 digits: 4096
possible keys)
Panel lock -
Enable command
Disables command from the
Display Panel
Commands
enabled
Commands enabled
Commands disabled
External
synchronisation
Selects the source of
synchronisation for the
inverter output
From bypass
line
From bypass line
From external input
From bypass line if within the limits; from
external input otherwise
External
temperature
Activates reading of the
external temperature probe
Disable
Disable
Enable (for floating voltage, only and not
Recharging)
Not modifiable compensation:
3,3 mV °C / Cell on the field 25-50°C
Communication
speed Slot 1
Communication speed for
serial port (Slot 1)
1200 bps
1200 bps (PRTK GPSER1
12
01..)
9600 bps (PRTK GPSER1
96
01..)
Communication
speed Slot 2
Communication speed for
serial port (Slot 2)
1200 bps
1200 bps (PRTK GPSER1
12
01..)
9600 bps (PRTK GPSER1
96
01..)