MULTI SENTRY
SPTMSTD2T16EREN
26
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
EXTERNAL I-O
I/O card model
Select the relay expansion
card type
MultiCOM 382
[4 out]
MultiCOM 382 [4 out]
MultiCOM 392 [8 out]
Input contact #3
mode
Input contact port setting
(AS400 port or
MultiCOM 382)
See software configuration manual
Output contact
#1-#2-#3-#4 mode
Output contact port setting
(AS400 port or
MultiCOM 382)
See software configuration manual
Output contact
#1 ÷ #8
Mode/Logic/Delay
Output contact port setting
(MultiCOM 392)
See software configuration manual
(#) Batteries voltage configuration
Battery custom
thresholds
Recharging voltage
±286 V
±260 ÷ ±300 V
Floating voltage
±273 V
±260 ÷ ±300 V
Battery low voltage
±220 V
±210 ÷ ±240 V
End discharge voltage
±204 V
±190 ÷ ±230 V
Recharging current
12 %
3 ÷ 50 %
10.
UPS CABINET
The cabinet is made of galvanised steel with an IP20 rating (degree of Ingress Protection), even with the front
door open.
Ventilation is forced and is guaranted by fans located on the back; air intake is front to rear, output is on the
back.
The main assemblies (including the power module) are temperature monitored.