MULTI SENTRY
SPTMSTD2T16EREN
31
b)
Transformer located outside the UPS
(depending on the requirements and the type of electrical set up
described below).
This option can be applied to the entire 10÷40 kVA range.
Note:
The presence of the transformer inside the UPS changes the neutral system. The eventual installation of a
"maintenance bypass remote" in parallel to the UPS is incompatible with the presence of the transformer. If it is still
inserted by pass the remote maintenance, make sure that simultaneously with the closing of the switch by-pass
the UPS is insulated from the plant by opening the disconnectors of input / output.
Electric connections diagrams
The following drawings just provide a general overview of the possible installation scenarios.
Every configuration should be carefully evaluated according with the real installation environment.
Note:
the presence of the transformer will modify the neutral arrangements of the installation. The eventual
installation of a "remote maintenance bypass" to the insulation of the UPS, in case of breakdown / maintenance
will take place after the transformer (if the same is installed in the UPS input) or upstream of the transformer (if the
same is installed in the UPS output).
UPS with no variation neutral condition
UPS with Galvanic insulation on the input
UPS with Galvanic insulation on the output