MULTI SENTRY
SPTMSTD2T16EREN
25
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
BATTERY
UPS without
battery
Operating mode without
batteries (for converters or
voltage stabilizers)
Operating with
Batteries
With Batteries
Without Batteries
Battery low time
Estimated autonomy time
r
emaining for “battery low”
warning
3 min.
1 - 255 @1 min step
Autorestart
voltage
Minimum Battery voltage for
automatic restart
236 V
200 ÷ 260 @ 1 V step
Automatic
battery test
Interval of time for the
automatic battery test
40 hours
Disabled
1 ÷ 273 hours @ 1 hour step
1 ÷ 39 day at defined hour
Defined day and hour within the month
Parallel common
battery
Common Battery for parallel
UPS systems
Disable
Disable
Enable
Internal battery
capacity
Nominal Battery capacity for
internal batteries
Change
according with
UPS model
0 - 18 Ah @1 Ah step
External battery
capacity
Nominal Battery capacity for
external batteries
7 Ah for UPS
without internal
batteries;
0 Ah all other
cases
0 ÷ 999 @ 1 Ah step
Battery charging
algorithm
Algorithm and Battery
recharging threshold
(#)
Two levels
Floating
Two levels
Cycling recharge
Customised
Battery
recharging
current
Recharging current compare
to battery nominal capacity
(%)
12%
3 ÷ 50 @ 1% step
Internal charger
Nominal recharging current
for internal battery charger
Change
according with
UPS model
6 Amps
10 Amps
20 Amps
25 Amps
Additional
charger (external)
Nominal recharging current
for external battery charger
(not inside UPS)
0 A
0 ÷ 100 @ 1 Amp step