![Riello MCM 10 Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/riello/mcm-10/mcm-10_technical-specifications_1460115042.webp)
MULTI SENTRY
SPTMSTD2T16EREN
40
Electrical Specifications
UPS Power Modules (kVA)
10
12
15
20
30
40
SYSTEM
AC/AC Efficiency (On line)
Full load
93,5
93,6
94,0
94,0
96,1
96,0
Load 75%
93,0
93,3
93,8
94,0
96,2
96,2
Load 50%
91,8
92,4
93,0
93,8
96,1
96,2
Load 25%
89,3
89,8
91,6
91,6
95,0
95,7
Auto-consumption
UPS on line mode without load [W]
220
220
240
240
240
240
UPS stand by without load [W]
110
110
110
110
113
113
Efficiency with UPS in ECO mode
Load 50%
98,2%
99,0%
Load 100%
98,4%
99,2%
Audible noise at 1 mt (according to EN
62040-3) -[dBA+/- 2 dBA]
<55 (A)
<50 (A)
Operating temperature
0 ± 40 ºC
Max. relative humidity during operation
90% (without condensation)
Max. installation altitude
1000 m at nominal power
(-1% reduction in power for every 100 m over 1000 m)
Max 4000 m
Power dissipated with resistive nominal
load (pf=0,9) and with battery charged*
0,63 kW
540
kcal/h
2150
B.T.U./h
0,75 kW
645
kcal/h
2560
B.T.U./h
0,86 kW
740
kcal/h
2940
B.T.U./h
1,15 kW
990
kcal/h
3930
B.T.U./h
1,28 kW
1101
kcal/h
4368
B.T.U./h
1,50 kW
1290
kcal/h
5120
B.T.U./h
Power dissipated with resistive nominal
load (0,9) and with battery under
recharge*
0,74 kW
637
kcal/h
2525
B.T.U./h
0,86 kW
740
kcal/h
2940
B.T.U./h
0,98 kW
843
kcal/h
3343
B.T.U./h
1,27 kW
1092
kcal/h
4333
B.T.U./h
1,33 kW
1143
kcal/h
4538
B.T.U./h
1,7 kW
1461
kcal/h
5800
B.T.U./h
UPS fan capacity
510 mc/h
626 mc/h
510 mc/h
Max current leaked to earth**
≤ 5 mA
≤ 50 mA
(4)
Data refers to typical load (75% kVA and pf 0,66)
*
3,97 B.T.U. = 1 kcal.
**
The leakage current of the load on the UPS adds to the protective earth conductor.