4
TECHNICAL DATA
(1)
Reference conditions: Ambient temperature 20°C - Barometer pressure 1000 mbar - Altitude 100 m a.s.l.
(2)
Acoustic pressure measured in manufacturer’s laboratory, with burner operating on test boiler at maximum output.
ELECTRICAL DATA
Motor IE1
Motor IE2
MODEL
RN 70
RN 100
RN 130
TYPE
636 T1
637 T1
638 T1
OUTPUT
(1)
DELIVERY
(1)
2nd stage
kW
456 - 798
40 - 70
684 - 1140
60 - 100
912 - 1481
80 - 130
kg/h
1st stage
kW
kg/h
228 - 456
20 - 40
342 - 684
30 - 60
456 - 912
40 - 80
FUEL
OIL, viscosity max. at 50 °C: 150 cSt - 20 °E
OPERATION
•Intermittent (min. 1 stop in 24 hours).
•Two-stage (high and low flame).
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL PROTECTION
IP 44
CONFORMITY TO EEC DIRECTIVES
2004/108 - 2006/95 - 2006/42
NOISE LEVELS
(2)
dBA
75.0
77.0
78.5
MODEL
RN 70
RN 100
RN 130
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral ~ +/-10%
50 - three-phase
FAN ELECTRIC MOTOR
rpm
V
kW
A
2800
230/400
1.1
4.7/2.7
2830
230/400
1.5
6.4/3.7
2860
230/400
2.2
8.5/4.9
PUMP ELECTRIC MOTOR
rpm
W
V
1400
320
220/240 - 380/415
1400
320
220/240 - 380/415
1400
320
220/240 - 380/415
Running current
A
1,55 0,9
1,55 0,9
1,55 0,9
Start-up current
A
6,8 3,93
6,8 3,93
6,8 3,93
HEATERS
W
8400
8400
8400
ELECTRICAL CONSUMPTION
kW max
2.0
2.6
3.2
MODEL
RN 70
RN 100
RN 130
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral ~ +/-10%
50 - three-phase
FAN ELECTRIC MOTOR
rpm
V
kW
A
2860
230/400
1.1
4.1/2.4
2860
230/400
1.5
5.5/3.4
2860
230/400
2.2
7.9/4.6
PUMP ELECTRIC MOTOR
rpm
W
V
1400
320
220/240 - 380/415
1400
320
220/240 - 380/415
1400
320
220/240 - 380/415
Running current
A
1,55 0,9
1,55 0,9
1,55 0,9
Start-up current
A
6,8 3,93
6,8 3,93
6,8 3,93
HEATERS
W
8400
8400
8400
ELECTRICAL CONSUMPTION
kW max
1.9
2.5
3.1
GB