background image

37

NOTE

Please refer to 3 - 3E and use the appropriate PPE when 

carrying out any of the actions or procedures contained within 

this section. 

8.1  CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, 

the relevant commissioning procedure must be undertaken to 

ensure the continued safe operation of the appliance. Particular 

attention should be made to ensure gas tightness, water 

tightness and the electrical integrity of the appliance.

8.2  APPLIANCE MODES OF OPERATION

NOTE

There must be sufficient 

system water pressure (min. 0.5 bar) 

to ensure the water pressure switch is activated. If there is in-

sufficient system pressure the pump and fan will be prevented 

from operating and the low-pressure fault code will be indicated.

8.2.1  MODE SELECTION IN THE OFF/RESET POSITION

When the mode selection is in the OFF/RESET position, the 

following functions are active.

Active functions

:

• frost-protection system

• pump & actuator anti-block.

8.2.2  ON-BOARD FUNCTIONS

• 

CO FUNCTION:

 the CO function when activated, will allow the 

appliance to run at CH maximum, DHW maximum or minimum 

output whilst a combustion analysis check or a mechanical gas 

valve calibration is being carried out. Whilst the CO function 

is active, all other functions are disabled (minimum power 

operating period, anti-cycle, set-point, etc). Once enabled, 

the CO function will remain active for a 15-minute period, or 

until the function is manually deactivated 

• 

FROST-PROTECTION: 

this function is only active when 

there are no requests for heating or HW. If the temperature 

drops below 5°C, the boiler will operate on minimum power 

until the temperature of the thermistors reaches 35°C for CH 

and 55°C for DHW. Thereafter the pump & fan will over-run 

for 30-seconds.

• 

ANTI-CYCLE FUNCTION:

 the anti-cycle function ensures the 

burner remains switched off for at least 3-minutes after the 

set-point hysterisis (set-point + 5-deg) for CH heat request.  

• 

PUMP ANTI-BLOCK FUNCTION: 

when there has been no 

heating or HW request for 24-hours, the anti-block cycle is 

activated. The pump will be activated for a period of 30-sec-

onds.

• 

ACTUATOR ANTI-BLOCK FUNCTION: 

when there has been 

no heating or HW request for 24-hours, the anti-block cycle 

is activated. The diverter

 valve actuator will motor briefly to 

the heating position, and then back to the DHW position. The 

pump will run briefly.

• 

DHW PRE-HEAT FUNCTION:

 when the DHW pre-heat func-

tion is enabled, the appliance will light periodically to maintain 

the temperature of the DHW heat exchanger. When the 

DHW thermistor and the primary thermistor fall below 35°C 

and 55°C respectively, the boiler will fire on m25% 

power until the primary thermistor exceeds 55°C. Thereafter 

the pump will over-run for a period of 30-seconds.

8.2.3  HEATING MODE

With the mode selection in the heating & hot water position 

and any additional controls (time clock, programmer, room 

thermostat, etc.) calling for heat, the appliance will operate 

in the heating mode. The pump and fan will be activated via 

the flow temperature sensor. When the fan is sensed to be 

operating correctly (tacho signal), the ignition sequence com-

mences. Ignition is sensed by the electronic circuit to ensure 

flame stability at the burner. Once successful ignition has been 

achieved, the electronic circuitry increases the gas rate to 75% 

for a period of 15 minutes.

The speed of the fan and therefore the output of the boiler is 

determined by the temperature of the water sensed by the flow 

temperature sensor, consequently a high temperature at the 

flow sensor results in a lower fan speed. 

As the water temperature increases, the temperature sensors 

– located on the flow pipe of the boiler – reduce the fan speed 

via the electronic circuitry. Depending on the load, either the 

water temperature will continue to rise until the set point is 

achieved or the water temperature will fall whereby fan speed 

will increase relative to the output required. When the boiler 

has reached the set point (+ hysterisis), the burner will switch 

off. The built-in anti-cycle device prevents the burner from re-

lighting for approximately 3-minutes. When the temperature 

of the flow sensor falls below the set point (- hysterisis), the 

burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the appli-

ance will re-attempt ignition a further 4-times then go to lockout. 

When the set-point has been reached (the position of the heating 

temperature selector) as measured at the primary thermistor, the 

appliance will begin the modulation phase whereby the fan and 

gas valve will continuously modulate to maintain the set-point.

If the temperature continues to rise and exceeds the set-point 

by 5°C (hysterisis), the burner will shut down. A new ignition 

sequence will be enabled when the 3- minute anti-cycle has 

been performed and the temperature at the primary thermistor 

has dropped 5°C (hysterisis) below the set-point.

8.2.4  DHW MODE

With the selector switch in either the hot water only or heating 

& hot water position, the appliance will operate in the hot water 

mode whenever a DHW outlet is opened. A flow rate exceeding 

2-litres per minute will activate the DHW flow switch whereupon 

the pump and fan will be activated via the flow temperature 

sensor. When the fan is sensed to be operating correctly (tacho 

signal), the ignition sequence commences. Ignition is sensed 

by the electronic circuitry to ensure flame stability at the burner. 

Once successful ignition has been achieved, the electronic 

circuit allows the gas rate to achieve the modulation value.

NOTE

When the request for heating and/or hot water has been satis-

fied, the appliance pump and fan may continue to circulate to 

dissipate any residual heat within the appliance.

ATTENTION

Gas type and appliance output 

must be set 

according to the 

specific appliance specification. Vokèra accepts no responsi

-

bility if the gas type is not correctly adjusted according to the 

respective appliance specification as detailed on the appliance 

data badge.

8.3  CHECKING THE CO

2

 AND ADJUSTING 

THE GAS VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED WITH THE 

AID OF A PROPERLY CALIBRATED FLUE GAS ANALYSER.

Isolate the appliance from the electrical supply and remove the 

appliance casing as described in 4.5. 

Set the flue gas analyser to read CO2 and insert the probe into 

the flue analysis test point. 

8.3.1  COMBUSTION CHECK

To carry out the combustion analysis, proceed as follows:

 

ƒ

set the boiler to the OFF status by pressing button 1 

 

ƒ

Remove the screw and the cover on the air distribution box 
(

A-B, 

Fig. 45

).

 

ƒ

Insert the flue gases analysis probe.

8  CHECKS, ADJUSTMENTS AND FAULT FINDING

Содержание 47-364-52

Страница 1: ...AINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK VISION PLUS High efficie...

Страница 2: ...22 5 OPERATION 23 5 1 ACCESS TO THE PARAMETERS 23 5 2 CONTROL PANEL 23 5 3 SETTINGS MENU TREE STRUCTURE 24 5 4 STARTING THE BOILER 25 5 5 BOILER CONFIGURATION 26 5 6 FIRST COMMISSIONING 28 5 7 VENT CY...

Страница 3: ...inated automatically 1 6a DIMENSIONS VISION PLUS 25C 30C HEIGHT 715 mm WIDTH 405 mm DEPTH 248mm Dear Customer Your Vok ra VISION PLUS boiler has been designed to meet and exceed the very latest standa...

Страница 4: ...indicator Indicates the presence of a flame in the event of a flame lockout the icon looks like Reset It comes on when there are alarms that require a manual reset by the user Enter It comes on when...

Страница 5: ...ns and the segments come on for 1sec and in sequence the firmware revision is displayed for 3sec Then the interface displays the status active at that moment If necessary the interface automatically g...

Страница 6: ...and the burner is lit the icon appears on the display Heating REQUEST the radiator icon blinks Bar 2 3 2a SUMMER MODE Set the boiler to the SUMMER status by pressing key 1 until the domestic hot water...

Страница 7: ...On the 4 digits a message scrolls containing the error code and its description DAY 2 3 8a RESET FUNCTION The RESET icon comes on when there is an alarm that requires a manual reset by the user for e...

Страница 8: ...ngineer 2 6a INFO MENU Pressing key 3 on the display screen displays a list of informa tion regarding the operation of the boiler listed by parameter name and value Passing from the display of one par...

Страница 9: ...DOWN THE SYSTEM FOR SHORT PERIODS The system and boiler can be shut down in the event of temporary absences weekends short breaks etc setting the boiler status to OFF 3a HOW TO While the electrical s...

Страница 10: ...secontactyournearestVok raoffice 4 2a WHAT IF I HAVE FREQUENTLY TO TOP UP THE SYSTEM If the system regularly requires topping up it may be indicative of a leak Please contact your installer and ask hi...

Страница 11: ...mer services VISION PLUS boiler complies with basic requirements of the following Directives Regulation EU 2016 426 Yield directive Article 7 2 and Annex III of directive 92 42 EEC Electromagnetic com...

Страница 12: ...r DHW flow switch Top AAV High limit thermostat Flow temperature sensor Safety valve DHWFilter Automatic by pass Return temperature sensor Water trans ducer Fig 5 2 DESIGN PRINCIPLES AND OPERATING SEQ...

Страница 13: ...25C VISION PLUS 30C Capacity 8 litres Maximum system volume 74 litres Pre charge pressure 1 bar Dimensions VISION PLUS 25C VISION PLUS 30C Height mm 715 Width mm 405 Depth mm 248 Dry weight kg 27 29 C...

Страница 14: ...ed 24 kW Seasonal space heating energy efficiency s 93 For boiler space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficie...

Страница 15: ...of 600 mm T Below an opening or window on a pitched roof 2000 mm V From a vertical terminal to an adjacent opening window air brick etc call Vokera technical for advice W From a vertical terminal to a...

Страница 16: ...PIPEWORK It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints Where possible pipes should have a gradient to ensure air is carried naturally to...

Страница 17: ...ed socket with a fused 3 pin plug both complying with BS 1363 is acceptable NOTE Note Vokera Ltd cannot guarantee the performance or reliability of the appliance if when it is supplied via an invertor...

Страница 18: ...4E AIR RELEASE POINTS These must be positioned at the highest points in the system where air is likely to be trapped They should be used to expel trapped air and allow complete filling of the system...

Страница 19: ...20132062 2000mm extension 2000mm 20131979 telescopic extension 372 519mm 522 plume management kit 1370mm 20135587 100mm flue brackets 5 N A Fig 12 Using the template A provided with the kit mark and d...

Страница 20: ...ONLY Using the template provided mark and drill a 125mm hole for the passage of the flue pipe The hole should be drilled LEVEL to ensure any condense fluid that forms is allowed to drain back to the a...

Страница 21: ...are located in the groove of the vertical flue connector Both screws C should now be tightened NOTE If more convenient the vertical flue connector can be attachedtotheverticalflueterminal extensionbe...

Страница 22: ...trical supply Connect the fly lead to a fused plug or fused isolator in the following way brown wire to LIVE supply blue wire to NEUTRAL supply green yellow to EARTH connection Insertthesupplied3 AMPf...

Страница 23: ...d it has the back cancel function A B Access to the domestic hot water comfort functions see para graph 5 8 9 Domestic hot water comfort function C It is normally used to raise the heating water tempe...

Страница 24: ...P4 05 PUMP CONTROL TYPE NOT USED P4 08 OT CASCADE CONTROL NOT AVAILABLE ON THIS MODEL P4 09 SCREED FUNCTION 0 1 INSTALLER 0 P4 10 ANTI CYCLE FUNCTION 0 20min INSTALLER 3min P4 11 RESET CH TIMERS 0 1 I...

Страница 25: ...ITY P8 01 BUS 485 CONFIG 0 1 2 SERVICE 0 P8 03 OT CONFIG 0 1 SERVICE 1 5 4 STARTING THE BOILER Ensure that steps 6 1 through to 6 6 have been completed be fore supplying the gas and electrical supply...

Страница 26: ...oard for calculating the ignition delivery temperature of the burner IGNITION TEMPERATURE HEATING SETPOINT P4 04 The factory setting for this parameter is 3 C it can be changed within the 2 10 C range...

Страница 27: ...eet of the BE16 accessory board for more information about the use of this parameter P4 25 When P4 12 1 this parameter allows you to set the hydraulic configuration of heating zone 1 The factory setti...

Страница 28: ...ntil the icon for the desired function is displayed 5 8 1 WINTER MODE Set the boiler to the WINTER status by pressing key 1 until both the domestic hot water icon and the heating icon are displayed Th...

Страница 29: ...in the preset range in steps of 0 5 C The level bars beside the heating icon show the setpoint value set with respect to the operating range four bars on max setpoint one bar on min setpoint 5 8 7 SAF...

Страница 30: ...t the P4 menu and then P4 09 with the keys confirming the selection with Note SCREED HEATING is not available if the boiler is a status other than OFF To activate the function set the parameter to 1 t...

Страница 31: ...e Drain the boiler and system from the lowest points Open the drain valve full bore to remove any installation debris from the boiler prior to lighting Refill the boiler and heating system as describe...

Страница 32: ...mperature can be adjusted between 37 C 60 C via the buttons A B Fig 1 6 11 SETTING THE SYSTEM DESIGN PRESSURE The design pressure should be a minimum of 0 5 bar and a maximum of 1 5 bar The actual rea...

Страница 33: ...m pump base and lift pump assembly clear of the hydraulic manifold The pump assembly can now be removed from the appliance Replace carefully in the reverse order 7 7 SAFETY VALVE FIG 32 Carry out comp...

Страница 34: ...front cover Disconnect the electrode leads and ancillary wiring from their respective connectors Re move the retaining screws V for electrode Remove the spark ignition electrode W Remove the flame sen...

Страница 35: ...fully withdraw the by pass cartridge S1 and or DHW non return cartridge T1 Ensure all seals are in good condition taking care to ensure they are replaced correctly Replace in the reverse order ensurin...

Страница 36: ...component removal procedure as described in 7 4 Disconnect the electrical plug from the actuator H2 Replace in the reverse order 7 21 4 DHW THERMISTOR FIG 33 Carry out component removal procedure as d...

Страница 37: ...er Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15 minutes The speed of the fan and therefore the output of the boiler is determined...

Страница 38: ...own on the display IMPORTANT The combustion analysis function is active for a maximum time of 15 minutes the burner shuts down if an outlet temperature of 95 C is reached It will ignite again when the...

Страница 39: ...isconnection and re connection of any electrical wiring or component these checks must be repeated 8 7 FAULT FINDING Before attempting any fault finding the electrical checks as detailed in 8 6 must b...

Страница 40: ...14 15 16 17 18 19 20 21 22 23 24 25 26 Giri ven latore r p m Portata termica kW Curva portata termica giri ven latore Caldaia Vision PLUS 25C Qm Qn RANGE RATED HTG curve VISION PLUS 25C heat output kW...

Страница 41: ...0 15 20 CORREZIONE CURVA CLIMATICA CLIMATE CURVE CORRECTION EXTERNAL TEMPERATURE C DELIVERY TEMPERATURE C NIGHT COMPENSATION PARAMETER P4 20 If a ROOM THERMOSTAT is connected to a programming timer fr...

Страница 42: ...his latter is replaced The total hours can be verified in the following way access the INFO menus as indicated in the paragraph 8 15 INFO menu at I0 15 to display the value of the flue gases probe met...

Страница 43: ...n P4 12 1 I0 14 ZONE 1 OUTLET Zone 1 ow sensor value when P4 13 1 I0 15 EXHAUST PROBE HOURS Number of hours the heat exchanger has been operating in condensing mode I0 16 MAIN ZONE SET Main zone deliv...

Страница 44: ...following figure Using the arrows select the day or the pre selected group of days 1 2 3 4 5 6 7 programming of the individual days 1 5 programming from Monday to Friday 6 7 programming from Saturday...

Страница 45: ...er must always be supplied with a permanent 230V electrical supply The room thermostat connection is low voltage 24 Vdc Do not connect any controls or auxiliary equipment to the low voltage terminal s...

Страница 46: ...brown blue CN3 1 2 NOTE L N E connection is advisable 7 1 CN9 D H W T D H W F S red red violet violet t 3 CN4 1 brown heat black D H W blue Heat 3 D H W 1 N 2 3W TSC2 S E N F 3 yellow green blue brown...

Страница 47: ...he boiler to propane gas G31 use the specific accessory kits For disassembly refer to the instructions below remove the power supply to the boiler and close the gas tap remove the casing as indicated...

Страница 48: ...section 7 3 set boiler to operate at minimum rate to minimum load condition Allow sufficient time for combustion to stabilise YES I Is s C CO O 3 35 50 0p pp pm m a an nd d C CO O C CO O2 2 r ra at ti...

Страница 49: ...urers recommendations at least annually This must be carried out by a competent Gas Safe registered engineer The service details should be recorded on the Benchmark Service and Interim Boiler Work Rec...

Страница 50: ...no what is the maximum central heating output selected kW Dynamic gas inlet pressure mbar C Central heating return temperature C System correctly balanced rebalanced Yes COMBINATION BOILERS ONLY Is th...

Страница 51: ...er name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas r...

Страница 52: ...er name Company name Telephone No Gas Safe registration No Max rate CO ppm CO CO CO Min rate CO ppm CO CO CO undertaken in accordance with manufacturers instructions and readings are correct yes Gas r...

Страница 53: ...structions must be provided e g Benchmark Service Record If this condition is not met the period of warranty will extend to only 12 months from date of installation By registering your appliance you w...

Страница 54: ...from a Trading Standards Authority or a Citizen Advice Bureaux Your Personal Details Vok ra takes care of your personal details in order to protect your privacy Below we detail how we use any data you...

Страница 55: ...Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the right to change specification without prior notice Consumers statutory rights are not affected Company Reg...

Отзывы: